Hipulse - Single Phase ‘1+N’ UPS System

130 kVA - 110V

BATTERY TEST

 

GENERATOR

 

PANEL SETUP

 

>NEXT PAGE

<

PROTOCOLS

ON/OFF UPS CONTROLS RELOAD UPS DATA

>RESET BUFFERS <

RESET ALARM HISTORY RESET EVENT HISTORY

RECTIFIER OFF

 

>RESET ALARMS

<

Select NEXT PAGE and press ENTER key.

Press the ENTER key.

Select RESET ALARMS and press ENTER key.

Return the Display window to normal by repeatedly pressing the ESCAPE key back through the various windows until the default screen is displayed.

These operations resets the logic circuitry to enable the rectifier, inverter and static switch to operate normally.

Note: When the remote EPO switch has been activated it is necessary to manually close the battery circuit breaker.

CAUTION

When the EPO system incorporates a trip facility of the external input a.c. power supply circuit breaker, the RESET switch would have no affect on it. First close the external input a.c. supply circuit breaker, the UPS can be started in the normal manner, as the logic circuits will automatically reset on return of the power supplies.

5.8Adding a single module to an existing system

This procedure should be carried out only by trained service personal.