Liebert 130 kVA Display Panel message interpretation in 1+N System, Complete system shutdown

Models: 130 kVA

1 102
Download 102 pages 29.34 Kb
Page 90
Image 90

User Manual

Hipulse - Single Phase ‘1+N’ UPS System

130 kVA - 110V

8.3.1.5 Switching ON a UPS that was previously switched OFF and isolated from the system.

1.Close the circuit-breakers relative to the shutdown UPS that were previously opened on the power distribution switchboard.

2.Close the switches Q1 (rectifier input) and Q2 (bypass input) of the UPS.

3.Select the MEASUREMENT function from the display on the main menu, then press ENTER and select BATTTERY. Press ENTER and check that the voltage level has reached the rated value (432V or 446 or 459 in accordance with no. of battery blocks).

4.Close the battery circuit-breaker.

5.Close the UPS switch Q4 (output), wait about 20 seconds and check the message NORMAL OPERATION appearing on the display operator panel.

8.3.1.6 Complete system shutdown

Follow the procedure described in Chapter 5 - Operating Instruction : paragraph 5.6 by working on several UPS modules.

8.3.1.7 Complete system reset

Follow the procedure described in Chapter 5 - Operating Instruction : paragraph 5.7 by working on several UPS modules.

8.4Display Panel message interpretation in '1+N' System

The alarms are the same as for the single module, as given in the previous paragraph, with the additional alarms:

CODE

DISPLAY ALARM MESSAGE

INTERPRETATION

44

INV: PARALLEL ERROR

The parallel board has detected a wrong sharing of the load and

 

 

has blocked its inverter. Seek qualified assistance.

46

NR: INVERTERS NOT OK.

The number of active inverters is below the preset capacity value.

70