User Manual
Hipulse - Single Phase ‘1+N’ UPS System | 130 kVA - 110V |
CHAPTER 2
Installation Procedure
2.1Introduction
WARNING
Do not apply electrical power to the UPS equipment before the arrival of the commissioning engineer.
WARNING
The UPS equipment should be installed by a qualified engineer in accordance with the information contained in this chapter and all equipment not referred to this manual is shipped with the details its own mechanical and electrical installation.
WARNING - Battery Hazards
∙Special care should be taken when working with the batteries associated with this equipment. When connected together, the battery terminal voltage will exceed 400V DC, and is potential lethal.
∙Eye protection should be worn to prevent injury from accidental electrical arcs.
∙Remove rings, watches and all metal objects.
∙Only use tools with insulated handles.
∙Wear rubber gloves.
∙If a battery leaks electrolyte, or is otherwise physically damaged, it must be replaced, stored in container resistant to sulfuric acid and disposed of in accordance with local regulations.
∙If electrolyte comes into contact with the skin, the affected area should be washed immediately with water.
NOTE
The UPS System can be connected to an IT (isolated neutral) power system
This section describes the UPS system’s environmental requirements and mechanical considerations that must be taken into account when planning the positioning and cabling of the UPS equipment.
Because every site has its peculiarities, it is not the aim of this chapter to provide