Table 13 — Troubleshooting
| FAULT | HEATING | COOLING | POSSIBLE CAUSE | SOLUTION | |
Main Power Problems | X | X | Green Status LED Off | Check line voltage circuit breaker and disconnect. | ||
|
|
|
|
| Check for line voltage between L1 and L2 on the contactor. | |
|
|
|
|
| Check for | |
|
|
|
|
| Check primary/secondary voltage on transformer. | |
HP Fault — Code 2 |
| X | Reduced or no water flow in | Check pump operation or valve operation/setting. | ||
High Pressure |
|
| cooling | Check water flow adjust to proper flow rate. | ||
|
|
|
|
| ||
|
|
| X | Water temperature out of range | Bring water temperature within design parameters. | |
|
|
|
| in cooling |
| |
|
| X | X | Overcharged with refrigerant | Check superheat/subcooling vs. typical operating condition. | |
|
| X | X | Bad HP switch | Check switch continuity and operation. Replace. | |
LP/LOC Fault — Code 3 | X | X | Insufficient charge | Check for refrigerant leaks. | ||
Low Pressure/Loss of |
|
|
|
| ||
X |
| Compressor pump down at | Check charge and | |||
Charge |
| |||||
|
|
| ||||
|
|
|
|
| ||
FP1 Fault — Code 4 | X |
| Reduced or no water flow in | Check pump operation or water valve operation/setting. | ||
Source Water Freeze |
|
| heating |
| ||
|
| Plugged strainer or filter. Clean or replace. | ||||
Protection |
|
|
| |||
|
|
| Check water flow adjust to proper flow rate. | |||
|
|
|
|
| ||
|
| X |
| Inadequate antifreeze level | Check antifreeze density with hydrometer. | |
|
| X |
| Improper freeze protect setting | Clip JW3 jumper for antifreeze | |
|
|
|
|
| ||
|
| X |
| Water temperature out of range | Bring water temperature within design parameters. | |
|
| X | X | Bad thermistor | Check temperature and impedance correlation. | |
FP2 Fault — Code 5 |
| X | Reduced or no water flow in | Check pump operation or water valve operation/setting. | ||
Load Coil Freeze |
|
| heating |
| ||
|
| Plugged strainer or filter. Clean or replace. | ||||
Protection |
|
|
| |||
|
|
| Check water flow adjust to proper flow rate. | |||
|
|
|
|
| ||
|
|
| X | Improper freeze protect setting | Clip JW3 jumper for antifreeze | |
|
|
|
|
| ||
|
|
| X | Water temperature out of range | Bring water temperature within design parameters. | |
|
| X | X | Bad thermistor | Check temperature and impedance correlation. | |
Over/Under Voltage — | X | X | Under voltage | Check power supply and | ||
Code 7 |
|
|
|
| ||
|
|
| Check power supply wire size. | |||
(Auto Resetting) |
|
|
| |||
|
|
| Check compressor starting. | |||
|
|
|
|
| ||
|
|
|
|
| Check | |
|
| X | X | Over voltage | Check power supply voltage and | |
|
|
|
|
| Check | |
Performance Monitor — | X |
| Heating mode FP2>51.7 C | Check for overcharged unit. | ||
Code 8 |
|
|
|
| ||
| X | Cooling mode FP1>51.7 C OR | Check for poor water flow or airflow. | |||
|
|
| ||||
|
|
|
| FP2< 4.4 C |
| |
No Fault Code Shown | X | X | No compressor operation | See scroll compressor rotation section. | ||
|
| X | X | Compressor overload | Check and replace if necessary. | |
|
| X | X | Control board | Reset power and check operation. | |
Unit Short Cycles | X | X | Unit in Test mode | Reset power or wait 20 minutes for auto exit. | ||
|
| X | X | Unit selection | Unit may be oversized for space. Check sizing for actual load of space. | |
|
| X | X | Compressor overload | Check and replace if necessary. | |
Unit Does Not Operate in |
| X | Reversing valve | Set for cooling demand and check | ||
Cooling |
|
|
|
| ||
|
|
| If RV is stuck, run high pressure up by reducing water flow and while operat- | |||
|
|
|
|
| ||
|
|
|
|
| ing engage and disengage RV coil voltage to push valve. | |
|
|
| X | Thermostat setup | Check for ‘O’ RV setup not ‘B’. | |
|
|
| X | Thermostat wiring | Check O wiring at heat pump. Jumper O and R for RV coil. | |
Insufficient Capacity/ | X | X | Low refrigerant charge | Check superheat and subcooling. | ||
Not Cooling or Heating |
|
|
|
| ||
X | X | Restricted metering device | Check superheat and subcooling. Replace. | |||
Properly | ||||||
| X | Defective reversing valve | Perform RV touch test. | |||
|
|
| ||||
|
| X | X | Thermostat improperly located | Check location and for air drafts behind thermostat. | |
|
| X | X | Unit undersized | Recheck loads and sizing. Check sensible cooling load and heat pump | |
|
|
|
|
| capacity. | |
|
| X | X | Scaling in water heat exchanger | Perform scaling check and clean if necessary. | |
|
| X | X | Inlet water too hot or cold | Check load, loop sizing, loop backfill, ground moisture. | |
High Head Pressure |
| X | Scaling in water heat exchanger | Perform scaling check and clean if necessary. | ||
|
| X | X | Unit overcharged | Check superheat and subcooling. Reweigh in charge. | |
|
| X | X | Vacuum system and reweigh in charge. | ||
|
| X | X | Restricted metering device | Check superheat and subcooling. Replace. | |
Low Suction Pressure | X |
| Reduced water flow in heating | Check pump operation or water valve operation/setting. | ||
|
|
|
|
| Plugged strainer or filter. Clean or replace. | |
|
|
|
|
| Check water flow adjust to proper flow rate. | |
|
| X |
| Water temperature out of range | Bring water temperature within design parameters. | |
| LEGEND |
|
|
|
| |
FP | — Freeze Protection |
|
|
|
| |
HP | — High Pressure |
|
|
|
| |
LED — |
|
|
|
| ||
LOC — Loss of Charge |
|
|
|
| ||
LP | — Low Pressure |
|
|
|
| |
RV | — Reversing Valve |
|
|
|
|