Step 6 — Wire Electrical Connections
WARNING
To avoid possible injury or death due to electrical shock, open the power supply disconnect switch and secure it in an open position during installation. Install lockout tag.
CAUTION
Use only copper conductors for
All
Operating voltage must be the same voltage and phase as shown in Table 3.
Refer to unit wiring diagrams Fig.
Consult the unit wiring diagram located on the inside of the compressor access panel to ensure proper electrical hookup. The installing (or electrical) contractor must make the field connections when using
Make all final electrical connections with a length of flexi- ble conduit to minimize vibration and sound transmission to the building.
POWER CONNECTION — Line voltage connection is made by connecting incoming line voltage wires to L1, L2, and L3 on the power distribution block.
SUPPLY VOLTAGE — Operating voltage to unit must be within voltage range indicated on unit nameplate.
Voltages between phases must be balanced within 2%. Use the following formula to determine the percentage voltage imbalance:
% Voltage Imbalance
= 100 x | max voltage deviation from average voltage |
| average voltage |
Example: Supply voltage is
AB = 372 volts
BC = 376 volts
AC = 384 volts
Average Voltage = | 372 + 376 + 384 | |
3 | ||
|
= 1132 3
= 377
Determine maximum deviation from average voltage:
(AB) 372 – 377 = 5 v (BC) 376 – 377 = 1 v (AC) 384 – 377 = 7 v
Maximum deviation is 7 v. Determine percent voltage imbalance.
% Voltage Imbalance = | 100 x |
| 7 |
| 377 | ||
= | 1.86% |
|
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
Operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electri- cal components.
NOTE: If more than 2% voltage imbalance is present, contact local electric utility.
Table 3 — 50PSW Electrical Data
50PSW UNIT | VOLTAGE |
| VOLTAGE RANGE | COMPRESSOR |
| TOTAL | MCA | MOCP* | |||
| SIZE |
| MIN/MAX | RLA | LRA |
| QTY | FLA | |||
|
|
|
|
| |||||||
| 036 |
| 198/264 | 13.5 | 67 |
| 1 | 13.5 | 16.9 | 30 | |
|
| 342/462 | 5.4 | 38 |
| 1 | 5.4 | 6.8 | 15 | ||
|
|
|
| ||||||||
| 060 |
| 198/264 | 24.5 | 153 |
| 1 | 24.5 | 30.6 | 50 | |
|
| 342/462 | 9.6 | 74 |
| 1 | 9.6 | 12.0 | 20 | ||
|
|
|
| ||||||||
| 120 |
| 198/264 | 24.5 | 153 |
| 2 | 49.0 | 55.1 | 80 | |
|
| 342/462 | 9.6 | 74 |
| 2 | 19.2 | 21.6 | 30 | ||
|
|
|
| ||||||||
| 180 |
| 198/264 | 44.9 | 273 |
| 1 | 44.9 | 56.1 | 100 | |
|
| 342/462 | 18.6 | 118 |
| 1 | 18.6 | 23.3 | 40 | ||
|
|
|
| ||||||||
| 360 |
| 198/264 | 44.9 | 273 |
| 2 | 89.8 | 101.0 | 125 | |
|
| 342/462 | 18.6 | 118 |
| 2 | 37.2 | 46.6 | 60 | ||
|
|
|
| ||||||||
|
| LEGEND |
|
|
|
|
|
|
|
| |
FLA | — Full Load Amps |
|
|
|
|
|
|
|
| ||
HACR — Heating, Air Conditioning, and Refrigeration |
|
|
|
|
|
|
| ||||
LRA — Locked Rotor Amps |
|
|
|
|
|
|
|
| |||
MCA — Minimum Circuit Amps |
|
|
|
|
|
|
|
| |||
MOCP — Minimum Overcurrent Protection |
|
|
|
|
|
|
|
| |||
RLA | — Rated Load Amps |
|
|
|
|
|
|
|
|
7