L1 L2 L3
Grnd Power Distribution
Block Transformer
Connector
Low Voltage
C Control #1
Contactor
Connector
Low Voltage
C Control #2
Fig. 8 — Typical Field Wiring
EXTERNAL LOOP POWER CONNECTION — If the unit is to be connected to an external loop pump or flow controller, connect the pump to the loop pump terminal block PB1. The maximum power handling is 4 amps at
Step 7 — Wire Low Voltage Connections
THERMOSTAT CONNECTIONS
The thermostat should be wired directly to the Aquazone™ control board. See Fig.
WATER FREEZE PROTECTION — The Aquazone control allows the field selection of source fluid freeze protection points through jumpers. The factory setting of jumper JW3 (FP1) is set for water at
Fig. 9 — Typical Aquazone Control Board
Jumper Locations (Complete C Control Shown)
ACCESSORY CONNECTIONS — The terminal labeled A on the control is provided to control accessory devices such as water valves, electronic air cleaners, humidifiers, etc. This sig- nal operates with the compressor terminal. See Fig. 10. Refer to the specific unit wiring schematic for details.
Terminal Strip
C
Typical
24 VAC Water
Valve
A
Fig. 10 — Typical Aquazone Accessory Wiring
(Deluxe D Control Shown)
NOTE: The A terminal should only be used with
IMPORTANT:
WATER SOLENOID VALVES — Water solenoid valves may be used on variable flow systems and ground water instal- lations. A typical well water control valve wiring which can limit waste water in a lockout condition is shown in Fig. 10. A slow closing valve may be required to prevent water hammer. When using a slow closing valve, special wiring conditions need to be considered. The valve takes approximately 60 sec- onds to open (very little water will flow before 45 seconds) and it activates the compressor only after the valve is completely opened by closing its end switch. When wired as shown, the valve will have the following operating characteristics:
1.Remain open during a lockout.
2.Draw approximately 25 to
IMPORTANT: This can overheat the anticipators of electromechanical thermostats. Only use relay based electronic thermostats.
PRE-START-UP
System Checkout — When the installation is complete, follow the system checkout procedure outlined below before starting up the system. Be sure:
1.Voltage is within the utilization range specifications of the unit compressor and fan motor, and voltage is balanced for
2.Fuses, breakers and wire are correct size.
3.Low voltage wiring is complete.
4.Piping and system flushing is complete.
5.Air is purged from closed loop system.
6.System is balanced as required. Monitor if necessary.
7.Isolation valves are open.
8.Water control valves or loop pumps are wired.
9.Transformer switched to lower voltage tap if necessary.
10.Service/access panels are in place.
11.Control
12