Watchdog Features

Overview

To detect internal problems and recover from unanticipated inputs, the Rack PDU uses internal, system- wide watchdog mechanisms. When it restarts to recover from an internal problem, a System: Warmstart event is recorded in the event log.

Network interface watchdog mechanism

The Rack PDU implements internal watchdog mechanisms to protect itself from becoming inaccessible over the network. For example, if the Rack PDU does not receive any network traffic for 9.5 minutes (either direct traffic, such as SNMP, or broadcast traffic, such as an Address Resolution Protocol [ARP] request), it assumes that there is a problem with its network interface and restarts.

Resetting the network timer

To ensure that the Rack PDU does not restart if the network is quiet for 9.5 minutes, the Rack PDU attempts to contact the default gateway every 4.5 minutes. If the gateway is present, it responds to the Rack PDU, and the response restarts the 9.5-minute timer. If your application does not require or have a gateway, specify the IP address of a computer that is running on the network and is on the subnet. The network traffic of that computer will restart the 9.5-minute time frequently enough to prevent the Rack PDU from restarting.

Network Port Sharing

About the Network Port Sharing Feature

You can use the Network Port Sharing feature to view the status of and configure and manage up to four Rack PDUs using only one network connection. This is made possible by connecting the Rack PDUs via the "In" and "Out" ports on the Rack PDU front panel.

Note: All Rack PDUs in the group must be using the same Rack PDU firmware revision, 5.1.5 or later (excluding v6.0.5 EnergyWise), in order to support the Network Port Sharing Feature.

Display ID

The display ID is a number, 1 to 4, used to uniquely identify the Rack PDUs in a group. After two or more Rack PDUs are connected to one another in a group, they can be identified on the various interfaces by the use of this "Display ID". This Display ID is viewable on the LCD by selecting the Display Settings > Display ID > Show option on the LCD keypad.

Installation Instructions

Connect up to four Rack PDUs. Insert an RJ45 terminator (included) in the unused "In"/"Out" ports on each end of the chain.

Note: Failure to use terminators may cause a loss of communication on the Rack PDUs.

Note: To reduce the possibility of communication issues, the maximum total length of cabling connecting Rack PDUs in a group should not exceed 10 meters. All Rack PDUs in a Network Port Sharing group should reside in the same rack enclosure.

Connect the "Network" port of one of the grouped Rack PDUs to a network hub or switch. This unit will be the "Host" for the Rack PDU group. A Host is defined as a Rack PDU that is connected to the network and is part of a Rack PDU group. Set up network functionality for this Host Rack PDU as specified in the Establish Network Settings section. The Host will automatically discover any "Guest" PDUs connected via In/Out ports. The Rack PDU group is now available via the Host's IP address.

3

Switched Rack PDU User Guide

Page 12
Image 12
APC AP8941, AP89XX manual Watchdog Features, Network Port Sharing

AP89XX, AP8941 specifications

The APC AP8941 and AP89XX series are advanced power distribution units (PDUs) designed to meet the growing demands of modern data centers and IT environments. These PDUs are well-regarded for their reliability, efficiency, and ease of use, making them integral components for effective power management in critical applications.

One of the standout features of the AP8941 is its capability to provide both local and remote management. Equipped with a web interface, users can monitor power usage, track energy consumption, and gain insights into the performance of connected equipment from virtually anywhere. This remote capability is particularly beneficial for administrators managing multiple sites, as it enables efficient troubleshooting and minimizes downtime.

The AP8941 also supports environmental monitoring by integrating with temperature and humidity sensors. This feature ensures that data centers maintain optimal conditions to protect equipment from overheating or humidity-induced failures, thus enhancing the overall reliability of the power infrastructure.

Another significant aspect of the AP8941 is its ability to distribute power efficiently through its various outlet configurations. The flexible plug-and-play design allows users to customize their power distribution setups for diverse applications, accommodating unique configurations and equipment requirements.

Security is paramount in today’s IT landscape, and the AP89XX series addresses this concern through advanced security features. The units include user authentication and role-based access control, ensuring that only authorized personnel can access critical power management functionalities.

Additionally, the power visualization tools available with the AP8941 enable users to analyze real-time data, identify potential issues, and optimize their power usage. The sleek design and Mounting options make installation straightforward, whether horizontal or vertical, in standard racks or enclosures.

The series supports a variety of power input options and offers robust overload protection, which is essential for preventing damage to both the PDU and connected devices. The combination of management capabilities, security features, and real-time monitoring tools positions the APC AP8941 and AP89XX series as an excellent choice for IT professionals seeking reliable power management solutions in today's data-heavy environments.

In conclusion, the APC AP8941 and AP89XX offer a comprehensive suite of features that cater to the complex needs of data centers. With their focus on efficiency, security, and management capabilities, these PDUs serve as an essential part of modern IT infrastructure, ensuring operational continuity and power reliability.