SNMP traps

Trap Receivers.

Path: Administration > Notification > SNMP Traps > trap receivers

View trap receivers by NMS IP/Host Name. You can configure up to six trap receivers.

To configure a new trap receiver, click Add Trap Receiver.

To modify or delete a trap receiver, first click its IP address or host name to access its settings. (If you delete a trap receiver, all notification settings configured under Event Actions for the deleted trap receiver are set to their default values.)

To specify the trap type for a trap receiver, select either the SNMPv1 or SNMPv3 radio button. For an NMS to receive both types of traps, you must configure two trap receivers for that NMS, one for each trap type.

Item

 

Definition

 

 

 

Trap Generation

 

Enable (the default) or disable trap generation for this trap receiver.

 

 

 

NMS IP/Host Name

 

The IPv4/IPv6 address or host name of this trap receiver. The default, 0.0.0.0, leaves

 

 

the trap receiver undefined.

 

 

 

Language

 

Choose a language from the drop-down list. This can differ from the UI and from

 

 

other trap receivers.

 

 

 

SNMPv1 option.

 

 

 

 

Item

Definition

 

 

Community Name

The name (public by default) used as an identifier when SNMPv1 traps are sent to

 

this trap receiver.

 

 

Authenticate Traps

When this option is enabled (the default), the NMS identified by the NMS IP/Host

 

Name setting will receive authentication traps (traps generated by invalid attempts to

 

log on to this device). To disable that ability, unmark the checkbox.

 

 

 

SNMPv3 option. Select the identifier of the user profile for this trap receiver. (To view the settings of the user profiles identified by the user names selectable here, choose Network on the top menu bar and user profiles under SNMPv3 on the left navigation menu.)

See “SNMPv3” on page 89 for information on creating user profiles and selecting authentication and encryption methods.

SNMP Trap Test

Path: Administration > Notification > SNMP Traps > test

Last Test Result. The result of the most recent SNMP trap test. A successful SNMP trap test verifies only that a trap was sent; it does not verify that the trap was received by the selected trap receiver. A trap test succeeds if all of the following are true:

The SNMP version (SNMPv1 or SNMPv3) configured for the selected trap receiver is enabled on this device.

The trap receiver is enabled.

If a host name is selected for the To address, that host name can be mapped to a valid IP address.

To. Select the IP address or host name to which a test SNMP trap will be sent. If no trap receiver is configured, a link to the Trap Receiver configuration page is displayed.

95

Switched Rack PDU User Guide

Page 104
Image 104
APC AP8941, AP89XX manual Snmp traps, Snmp Trap Test

AP89XX, AP8941 specifications

The APC AP8941 and AP89XX series are advanced power distribution units (PDUs) designed to meet the growing demands of modern data centers and IT environments. These PDUs are well-regarded for their reliability, efficiency, and ease of use, making them integral components for effective power management in critical applications.

One of the standout features of the AP8941 is its capability to provide both local and remote management. Equipped with a web interface, users can monitor power usage, track energy consumption, and gain insights into the performance of connected equipment from virtually anywhere. This remote capability is particularly beneficial for administrators managing multiple sites, as it enables efficient troubleshooting and minimizes downtime.

The AP8941 also supports environmental monitoring by integrating with temperature and humidity sensors. This feature ensures that data centers maintain optimal conditions to protect equipment from overheating or humidity-induced failures, thus enhancing the overall reliability of the power infrastructure.

Another significant aspect of the AP8941 is its ability to distribute power efficiently through its various outlet configurations. The flexible plug-and-play design allows users to customize their power distribution setups for diverse applications, accommodating unique configurations and equipment requirements.

Security is paramount in today’s IT landscape, and the AP89XX series addresses this concern through advanced security features. The units include user authentication and role-based access control, ensuring that only authorized personnel can access critical power management functionalities.

Additionally, the power visualization tools available with the AP8941 enable users to analyze real-time data, identify potential issues, and optimize their power usage. The sleek design and Mounting options make installation straightforward, whether horizontal or vertical, in standard racks or enclosures.

The series supports a variety of power input options and offers robust overload protection, which is essential for preventing damage to both the PDU and connected devices. The combination of management capabilities, security features, and real-time monitoring tools positions the APC AP8941 and AP89XX series as an excellent choice for IT professionals seeking reliable power management solutions in today's data-heavy environments.

In conclusion, the APC AP8941 and AP89XX offer a comprehensive suite of features that cater to the complex needs of data centers. With their focus on efficiency, security, and management capabilities, these PDUs serve as an essential part of modern IT infrastructure, ensuring operational continuity and power reliability.