Troubleshooting

Rack PDU Access Problems

For problems that persist or are not described here, see the back cover of this manual.

Problem

Solution

 

 

Unable to ping the Rack PDU

If the Rack PDU’s Status LED is green, try to ping another node on the same

 

network segment as the Rack PDU. If that fails, it is not a problem with the Rack

 

PDU. If the Status LED is not green, or if the ping test succeeds, perform the

 

following checks:

 

• Verify all network connections.

 

• Verify the IP addresses of the Rack PDU and the NMS.

 

• If the NMS is on a different physical network (or subnetwork) from the Rack

 

PDU, verify the IP address of the default gateway (or router).

 

• Verify the number of subnet bits for the Rack PDU’s subnet mask.

 

 

Cannot allocate the

Before you can use a terminal program to configure the Rack PDU, you must shut

communications port through a

down any application, service, or program using the communications port.

terminal program

 

 

 

Cannot access the command line

Make sure that you did not change the baud rate. Try 2400, 9600, 19200, or 38400.

interface through a serial

 

connection

 

 

 

Cannot access the command line

• Make sure you are using the correct access method, Telnet or Secure SHell (SSH).

interface remotely

An Administrator can enable these access methods. By default, Telnet is enabled.

 

Enabling SSH automatically disables Telnet.

 

• For SSH, the Rack PDU may be creating a host key. The Rack PDU can take up to

 

one minute to create the host key, and SSH is inaccessible for that time.

 

 

Cannot access the Web interface

• Verify that HTTP or HTTPS access is enabled.

 

• Make sure you are specifying the correct URL — one that is consistent with the

 

security system used by the Rack PDU. SSL requires https, not http, at the

 

beginning of the URL.

 

• Verify that you can ping the Rack PDU.

 

• Verify that you are using a Web browser supported for the Rack PDU. See

 

“Supported Web Browsers” on page 52.

 

• If the Rack PDU has just restarted and SSL security is being set up, the Rack PDU

 

may be generating a server certificate. The Rack PDU can take up to one minute to

 

create this certificate, and the SSL server is not available during that time.

 

 

Cannot communicate using

• If you are having communications problems with Network Port Sharing, check

Network Port Sharing

that the total length of network cable between up to four units is not more than 10

 

meters.

 

• If you are having communications problems with Network Port Sharing, check

 

that a terminator is installed at both ends of up to four units that can be grouped

 

together.

 

• If you are using Network Port Sharing and do not see one or more of the units in

 

the group, check that all units in the group are using the same firmware revision.

 

You can download appropriate firmware revisions from the APC website.

 

 

Switched Rack PDU User Guide

114

Page 123
Image 123
APC AP89XX, AP8941 manual Troubleshooting, Rack PDU Access Problems, Problem Solution

AP89XX, AP8941 specifications

The APC AP8941 and AP89XX series are advanced power distribution units (PDUs) designed to meet the growing demands of modern data centers and IT environments. These PDUs are well-regarded for their reliability, efficiency, and ease of use, making them integral components for effective power management in critical applications.

One of the standout features of the AP8941 is its capability to provide both local and remote management. Equipped with a web interface, users can monitor power usage, track energy consumption, and gain insights into the performance of connected equipment from virtually anywhere. This remote capability is particularly beneficial for administrators managing multiple sites, as it enables efficient troubleshooting and minimizes downtime.

The AP8941 also supports environmental monitoring by integrating with temperature and humidity sensors. This feature ensures that data centers maintain optimal conditions to protect equipment from overheating or humidity-induced failures, thus enhancing the overall reliability of the power infrastructure.

Another significant aspect of the AP8941 is its ability to distribute power efficiently through its various outlet configurations. The flexible plug-and-play design allows users to customize their power distribution setups for diverse applications, accommodating unique configurations and equipment requirements.

Security is paramount in today’s IT landscape, and the AP89XX series addresses this concern through advanced security features. The units include user authentication and role-based access control, ensuring that only authorized personnel can access critical power management functionalities.

Additionally, the power visualization tools available with the AP8941 enable users to analyze real-time data, identify potential issues, and optimize their power usage. The sleek design and Mounting options make installation straightforward, whether horizontal or vertical, in standard racks or enclosures.

The series supports a variety of power input options and offers robust overload protection, which is essential for preventing damage to both the PDU and connected devices. The combination of management capabilities, security features, and real-time monitoring tools positions the APC AP8941 and AP89XX series as an excellent choice for IT professionals seeking reliable power management solutions in today's data-heavy environments.

In conclusion, the APC AP8941 and AP89XX offer a comprehensive suite of features that cater to the complex needs of data centers. With their focus on efficiency, security, and management capabilities, these PDUs serve as an essential part of modern IT infrastructure, ensuring operational continuity and power reliability.