Dip switches: input and outputs

The table below lists the four possible configurations, with their corresponding inputs and outputs.

Configuration 1

Configuration 2

Configuration 3 Configuration 4*

OFF-OFF-OFF-ON ON-OFF-OFF-ON

OFF-ON-OFF-ON

ON-ON-OFF-ON

Inputs

 

Device Actions

 

 

 

 

 

 

1

Turn the UPS on.

 

 

 

 

 

 

 

 

2

Turn the UPS off.

 

Turn the UPS off

 

 

 

 

safely.

See

 

 

 

 

Configuration

3

Start UPS self-test.

 

 

 

 

 

 

Utility

4

Shut down the UPS

Put the UPS in

Shut down the UPS

 

 

when on battery

bypass, if bypass is

when on battery

 

 

except for self-test or

available on the

except for self-test or

 

 

runtime calibration.

UPS.

runtime calibration.

 

 

 

 

 

 

Outputs

 

 

Device State

 

 

 

 

1

The UPS is on-battery (e.g., during a power failure, self-test, or

 

 

runtime calibration).

 

 

 

 

 

 

2

The UPS has a low battery.

 

 

 

 

 

3

The protected load is not receiving power from the UPS or

 

 

communication between the UPS and the Relay I/O Card has been

 

 

lost.

 

 

 

See

 

 

 

 

 

4

Replace the UPS battery.

UPS commanded to

Configuration

 

 

 

 

turn on

Utility

 

 

 

 

(echo of Input 1).

 

 

 

 

 

 

 

5

The UPS is

 

The UPS is in bypass

UPS commanded to

 

 

overloaded.

 

by selection from

turn off gracefully

 

 

 

 

software, front panel,

(echo of Input 2).

 

 

 

 

or rear panel.

 

 

 

 

 

 

 

 

6

Any UPS fault or

 

Any UPS fault, self-

Any UPS fault, self-

 

 

self-test failure.

 

test failure, or

test failure, overload,

 

 

 

or replace battery

 

 

 

 

overload.

 

 

 

 

 

 

 

 

 

 

* With this setup (the factory default), the Configuration Utility is used automatically.

8

 

Dry Contact I/O SmartSlot Card

 

Page 12
Image 12
APC AP9613, AP9810 manual Dip switches input and outputs, Configuration Configuration 3 Configuration