8Dry Contact I/O SmartSlot Card
Dip switches: input and outputs

The table below lists the four possible configurations, with their corresponding

inputs and outputs.

* With this setup (the factory default), the Configuration Utility is used automatically.

Configuration 1 Configuration 2 Configuration 3 Configuration 4*

OFF-OFF-OFF-ON ON-OFF-OFF-ON OFF-ON-OFF-ON ON-ON-OFF-ON
Inputs Device Actions
1 Turn the UPS on.
See
Configuration
Utility
2 Turn the UPS off. Turn the UPS off
safely.
3 Start UPS self-test.
4 Shut down the UPS
when on battery
except for self-test or
runtime calibration.
Put the UPS in
bypass, if bypass is
available on the
UPS.
Shut down the UPS
when on battery
except for self-test or
runtime calibration.
Outputs
Device State
1 The UPS is on-battery (e.g., during a power failure, self-test, or
runtime calibration).
See
Configuration
Utility
2 The UPS has a low battery.
3The protected load is not receiving power from the UPS or
communication between the UPS and the Relay I/O Card has been
lost.
4 Replace the UPS battery. UPS commanded to
turn on
(echo of Input 1).
5The UPS is
overloaded.
The UPS is in bypass
by selection from
software, front panel,
or rear panel.
UPS commanded to
turn off gracefully
(echo of Input 2).
6Any UPS fault or
self-test failure.
Any UPS fault, self-
test failure, or
overload.
Any UPS fault, self-
test failure, overload,
or replace battery