Command Reference: Switched Rack PDU
Command Line Interface (CLI) User’s Guide 29
pducoldstartdelay
Syntax (to read the cold-start delay):
pducoldstartdelay
Syntax (to set the cold-start delay):
pducoldstartdelay {time|never}
Description: Set or read the PDU cold-start delay
(the time that the Switched Rack PDU delays
applying power to the outlets after AC power has
been applied to the Switched Rack PDU).
Access: Administrator and device manager
(device-only user)
Parameters:
Output format, reading the cold start delay:
OK
PDU_name: PDU coldstart delay is time seconds.
Output format, setting the cold start delay:
OK
PDU_name: Setting PDU coldstart delay to time
seconds.
Error Messages: E101, E104
power
Syntax:
power
Description: Reads the total power usage of the
Switched Rack PDU in watts and volt-amps.
Parameters: None.
Access: All three user types with access to the
CLI.
Output Format:
OK
power_in_volt-ampsVA
power_in_wattsW
Error Message: 101
time The cold-start delay in seconds to set for the
Switched Rack PDU. Allowed values are 0
through 300.
never Sets the Switched Rack PDU to keep its
outlets turned off after power is applied until
the outlets are explicitly turned on by the on
command.