Operation

Basic Functions

Note: The LCD display interface screen and LEDs can be dimmed, using the Setup menu. Press any button on the front panel of the unit to illuminate the display screen and the LEDs.

Front panel buttons

Utility Source 122V 60Hz

Use the display interface on the front of the G50B-20A2 to configure and operate the unit.

Power. Push to apply power to the unit or to shut off power to the unit.

Status. Push to display the current status of the unit, including the current input/output voltage.

Setup. Push to scroll through the setup menus.

Up/Down. Push to change values (Setup menu) and browse menu pages (Status menu).

Display interface LEDs

There are eleven LEDs on the display interface.

LED

Illuminated

Not Illuminated

 

 

 

POWER ON

The unit is supplied with utility

There is no input utility power.

 

power.

 

LINE OK The utility power is within acceptable range, 92 V to 140 V.

The input voltage from utility power is outside the acceptable range and the unit has disconnected from utility power to protect the connected equipment.

PROTECTION The unit is protecting all connected

WORKING equipment.

The unit is not providing power protection. See Troubleshooting and contact APC Technical Support immediately.

WIRING OK The unit is functioning properly.

There is a problem with the building wiring. Contact a certified electrician.

OVERLOAD

The unit is overloaded. Disconnect

The unit is functioning properly.

 

some connected components.

 

 

Contact APC Technical Support.

 

 

 

DELAY 1

Power is being supplied to DELAY1. Power is not being supplied to DELAY1.

 

 

 

DELAY 2A

Power is being supplied to

Power is not being supplied to DELAY2A.

 

DELAY2A.

 

DELAY 2B Power is being supplied to

DELAY2B.

Power is not being supplied to DELAY2B.

DELAY 3

Power is being supplied to DELAY3.

Power is not being supplied to DELAY3.

DELAY 4

Power is being supplied to DELAY4.

Power is not being supplied to DELAY4.

 

 

 

SWITCHED

Power is being supplied to the

Power is not being supplied to the SWITCHED outlet.

 

SWITCHED outlet.

 

APC A/V G-Type Rack Power Filter: Operation

5

Page 9
Image 9