Temperature/Humidity Sensor (AP9335TH)

Specifications

Temperature accuracy

±2ºC (±3ºF), from 0 to 40ºC (32 to 104ºF)

Humidity accuracy

±4% RH, 20 to 90%

RH, at 25ºC (77ºF)

 

±8% RH, 30 to 80%

RH, from 15 to 30ºC

 

(59 to 95ºF)

 

Sensor operating temperature

–10 to 70ºC (14 to 159ºF)

Cable length

4 m (13 ft)

 

 

 

 

System Specifications

A-Link

Maximum combined length of all A-Link

1000 m (3,280 ft)

cables

 

 

 

Maximum number of NetBotz Rack

12

Sensor Pod 150s that can be cascaded on

 

the A-Link bus

 

Maximum number of sensors (sensors

8

with digital display [AP9520T] and

 

Temperature/Humidity Sensors with

 

Digital Display [AP9520TH]) that can be cascaded on the A-Link bus

Temperature/Humidity Sensor (AP9335TH), Temperature Sensor (AP9335T),

Maximum length of cable

15 m (50 ft)

 

 

Beacon

 

 

 

Maximum length of cable

100 m (330 ft)

NetBotz Dry Contact Cable (NBES0304),

NetBotz 3.65-m (12-ft) Door Switch Sensor for APC Racks (NBES0303),

NetBotz 15.24-m (50-ft) Door Switch Sensor for Rooms or Third Party Racks (NBES0302)

Maximum length of cable

30.48 m (100 ft)

If a combined total of ten or more devices (NetBotz Rack Sensor Pod 150s [NBPD0150], Temperature Sensors with Digital Display [AP9520T], and Temperature/Humidity Sensors with Digital Display [AP9520TH]) are cascaded on the A-Link bus, a supplemental power supply (Power Supply 100-120 Vac/24 VdcAP9505i) is required. The power supply connects to the 24 VDC Input on a NetBotz Rack Sensor Pod 150.

24

NetBotz Rack Monitor 200 Installation and Quick Configuration Manual

Page 28
Image 28
APC NBRK0200 configurationmanual Temperature/Humidity Sensor AP9335TH, System Specifications