23NetBotz Rack Monitor 200 Installation and Quick Configuration Manual
Specifications

NetBotz Rack Monitor 200 (NBRK0200)

Electrical
Input voltage, nominal, for AC Line Inlet 100–240 Vac; 50/60 Hz
Maximum total current draw for AC Line Inlet 10 A (defined by Switched Outlet load + 0.25 A)
Maximum output voltage for Switched Outlet Defined by input voltage
Maximum output current for Switched Outlet 10 A (defined by Switched Outlet load)
Voltage for Voltage Output contacts 12 Vdc, 24 Vdc
Current for Voltage Output contacts 75 mA total for 12 V or 24 V load
Current capacity of Relay Output contacts 1 A, 30 V AC/DC (rated for Class 2 circuits only)
Physical
Dimensions (H x W x D) 44.2 x 432.0 x 44.2 mm (1.74 x 17.00 x 1.74 in)
Shipping dimensions (H x W x D) 67 x 450 x 225 mm (2.6 x 17.8 x 8.9 in)
Weight 1.10 kg (2.50 lb)
Shipping weight 2.70 kg (6.00 lb)
Environmental
Elevation (above MSL)
Operating
Storage
0 to 3000m (0 to 10,000 ft)
0 to 15000 m (0 to 50,000 ft)
Temper ature
Operating
Storage
0 to 45ºC (32 to 113°F)
–15 to 65°C (5 to 149°F)
Humidity
Operating
Storage
0 to 95%, non-condensing
0 to 95%, non-condensing
Performance
Typical Rack Monitor 200 response time for dry
contact sensor or door switch sensor state changes
200 mS
Compliance
Approvals CE, C-UL tested to CSA C22.2 No. 60950-1-3, UL
60950-1, FCC Part 15 Class A, ICES-003 Class A,
VCCI Class A, EN 55022 Class A, EN 55024,
EN 61000-3-2, EN 61000-3-3, AS/NZS CISPR 22,
VDE tested to EN 60950–1