Precautions

Table 1:

SPD

Per Phase I2t

Iapparent

Ip

Ith

PM_3XS-B

175 kA2 seconds

17,000 A RMS

40,000 A RMS

220 A

PM_3XS-B CAUTION

LOSS OF SURGE SUPPRESSION

Do not energize the SPDs until the electrical system is completely installed, inspected, tested, and all conductors have been connected and functional, including the neutral.

Verify the voltage rating of the device and system before energizing the SPD.

Disconnect the SPD, including the neutral, from the power source before performing high-potential insulation testing or any tests where SPD components will be subjected to voltages higher than their rated turn-on voltage.

Failure to follow these instructions can result in injury or equipment damage.