APC PMP3XS-B, PMJ3XS-B, PMH3XS-B, PML3XS-B, PMG3XS-B, PMF3XS-B Grounding, Hazardous Touch Voltage

Models: PML3XS-B PMJ3XS-B PMH3XS-B PMF3XS-B PMP3XS-B PMG3XS-B

1 24
Download 24 pages 5.78 Kb
Page 12
Image 12
Grounding

Grounding

Grounding

HAZARDOUS TOUCH VOLTAGE WARNING

HAZARDOUS TOUCH VOLTAGE

Connect the SPD ground terminal to the building grounding grid structure.

Use an appropriately sized equipment grounding conductor.

When using metallic raceway or conduit:

Do not use the SPD ground unless augmented with an insulated equipment grounding conductor installed inside the metallic raceway or conduit.

Do not use isolated bushings to interrupt the metallic raceway or conduit.

Maintain electrical continuity at all raceway and conduit connections using appropriate bonding devices.

Do not use a separate isolated ground for the SPD.

Verify proper equipment connection to the grounding system.

Verify ground grid continuity by performing regularly scheduled inspections and testing as part of a comprehensive electrical maintenance program.

Failure to follow these instructions can result in death or serious injury.

The SPD has leakage current to ground when energized and can present a hazardous touch voltage.

The device has SPD elements connected from phase to ground. To prevent hazardous touch voltage on the SPD enclosure during normal operation or during SPD end-of-life, it is critical that there be a robust and effective connection to the building grounding structure. The grounding connection must utilize an equipment grounding conductor run with the phase and neutral (if present) connection of the power system. The SPD should not be connected to a separate isolated ground.

When metallic raceway is used as the wiring method, an insulated grounding conductor should be run inside the raceway and sized in accordance with all applicable codes. Maintain electrical continuity at all raceway connections using appropriate bonding devices and do not install isolating bushings to interrupt a metallic raceway run.

For best overvoltage suppression by the SPD, use a single-point ground system where the service entrance grounding electrode system is connected to and bonded to all other available electrodes, building steel, metal water pipes, driven rods, etc. (for reference, see IEEE 142-2007). The ground impedance measurement of the electrical system should be as low as possible, and in compliance with all applicable codes.

SPDs rated for use on solidly-grounded power systems must not be connected to resistance-grounded (for example HRG) or ungrounded power systems. Such a connection can result in damage to the components within the SPD.

12

Installation and Operation Manual

Page 12
Image 12
APC PMP3XS-B, PMJ3XS-B, PMH3XS-B, PML3XS-B, PMG3XS-B, PMF3XS-B operation manual Grounding, Hazardous Touch Voltage