SYMPTOM Gate will not open or close.
Control board in HARD SHUT DOWN mode.
Short the GND and UL connections on the lower left set of connectors and test.
Disconnect the solar panel or charger and measure the battery voltage. Battery should read 12 or more volts and never drop below 11 volts when gate is operating.
Reset program switches to factory settings. .
Single Boards
# 1, # 2, # 3, # 5, # 10 ON, all others OFF
Dual Boards
#1, # 2, # 5, # 10 ON, all others OFF Turn #9 ON for dual gate sync
1ON
2ON
3ON
4off
5ON
6off
7off
8off
9off
10ON
Disconnect all accessories from the circuit board - receivers, push buttons, keypads, loops, phones, intercoms, etc.
Activate the operator by momentarily shorting GND to INP on one of the three pin connectors.
If the operator works, reconnect each accessory individually starting with push button and test operation.
GND INP UT 12V
Momentarily short with a piece of wire or needle nose.
Disconnect actuator from circuit board and inspect pins in the connector for damage or poor connections.
Check for proper limit switch configuration (multimeter required) on the connector from the actuator:
GATE IN OPEN POSITION | Orange & Green wires are shorted, White & Green wires are open. |
GATE IN CLOSED POSITION .. | White & Green wires are shorted, Orange & Green wires are open. |
GATE IN MID TRAVEL | White, Green, & Orange wires are open, no shorts. |
|
|
|
|
Replace circuit board. |
|
22