Aprilaire 1850w Required Component, Preferred Basement Installation, Alternate Attic Installation

Models: 1830 1850w 1850

1 28
Download 28 pages 44.16 Kb
Page 10
Image 10
Required Component

DUCTING TO HVAC SYSTEM – BASEMENT AND ATTIC INSTALLATIONS

The Preferred Installation is to duct the dehumidifier to pull air from and return dehumidified air to the HVAC return duct.. This installation will ensure warm, dehumidified air is thoroughly mixed with the HVAC system air before being discharged into the living space.. Alternatively, the dehumidifier can be ducted to discharge to the supply duct, but the external static pressure of the HVAC system must not exceed 0.4”w.c. for the 1830 and 0.6”w.c. for the 1850/1850W.

Required Component

10” Ductwork

Figure 11 – Preferred Basement Installation

10” DUCT

 

AIR IS PULLED

HVAC/FURNACE

FROM AND

6 ft

SUPPLIED TO THE

RETURN DUCT

MIN

 

DEHUMIDIFIER

 

90-1886

Figure 13 – Preferred Attic Installation

 

PLENUM BOX OR Y-FITTING

AIR HANDLER

6 FT. MIN.

 

FILTER

 

10" DIA. INSULATED DUCT

Figure 12 – Alternate Basement Installation

Model 1850(W)

AIR IS DISCHARGED

0.6” w.c. MAX

TO SUPPLY DUCT

Model 1830

 

0.4” w.c. MAX

 

 

HVAC/FURNACE

AIR IS

 

PULLED FROM

 

RETURN DUCT

 

10” DUCT

90-1887

 

Figure 14 – Alternate Attic Installation

 

 

Model 1850(W)

 

 

 

0.6" w.c. MAX.

 

PLENUM BOX

 

Model 1830

PLENUM

 

 

0.4" w.c. MAX.

 

 

AIR HANDLER

 

 

24" MIN.

FILTER

 

 

 

 

BOTH SIDES

CONDENSATE PAN

90-1888

 

10" DIA. INSULATED DUCT BOTH SIDES

90-1889

CONDENSATE PAN

Ducting Notes:

Use insulated duct when the dehumidifier is located in an unconditioned space such as an attic or a garage.

Use a minimum of 12” of flex duct at the dehumidifier inlet and outlet to prevent vibration noise transmission.

When ducting return to return (preferred), the dehumidifier must be wired to turn on the HVAC fan when operating (see page 14).

When ducting return to supply, allow adequate space before the first branch duct to ensure the warm dehumidified air is thoroughly mixed with the HVAC system air..

10

Page 10
Image 10
Aprilaire 1850w, 1830 Required Component, Preferred Basement Installation, Alternate Basement Installation, Ducting Notes