Aprilaire 1830, 1850 Troubleshooting Guide, TROUBLESHOOTING continued, Symptom, Possible Reason

Models: 1830 1850w 1850

1 28
Download 28 pages 44.16 Kb
Page 26
Image 26
TABLE 5 – Troubleshooting Guide

TROUBLESHOOTING (continued)

TABLE 5 – Troubleshooting Guide

Symptom

Possible Reason

Troubleshooting Procedure

Dehumidifier does not

No power to unit..

• Check that the dehumidifier is plugged in.

 

 

 

turn on/run..

 

• Check that the power switch is turned ON.

 

 

 

 

 

• Check that the control is turned ON.

 

 

 

 

 

• Check that the circuit breaker has not tripped.

 

 

 

 

 

 

 

 

 

Dehumidifier blower is

Pressure drop across

• Check dehumidifier air filter and wash or replace.

 

 

 

running but with little or

dehumidifier is higher

• Check for blocked duct work and clear.

 

 

 

no airflow..

than 0.4”w.c. for Model

• Verify that the outlet collar with backflow damper is installed on the outlet side of the dehumidifier.

 

1830 or 0.6”w.c. for

 

• Check if backflow damper is blocked or stuck and remove obstruction.

 

 

 

Model 1850/1850W..

 

 

 

 

 

 

 

 

 

 

 

 

 

Dehumidifier blower is

Float switch open..

• If float switch installed, check connections at control board and empty condensate pan.

running but compressor

 

• If no float switch installed check that the jumper is installed at the float switch terminals on the

is not..

 

control board..

 

 

 

 

 

 

 

 

 

 

Coil frosting..

• Lack of or reduced airflow. Check dehumidifier air filter and wash or replace.

 

 

 

 

• Check for blocked duct work.

 

 

 

 

 

• Inlet air conditions below 60°F. Increase the humidity setting.

 

 

 

 

 

 

 

 

 

Inlet air temperature is

• Verify all ductwork is properly sealed.

 

 

 

 

outside of the 50°F –

 

 

 

 

 

104°F range or the dew

 

 

 

 

 

point is below 40°F and

 

 

 

 

 

there is a demand for

 

 

 

 

 

dehumidification..

 

 

 

 

 

 

 

 

 

 

When zoned, the

Incorrect damper wiring

• Verify wiring between dampers and 24 VAC transformer.

 

 

 

dehumidifier damper

or bad connection..

• If wired for Two Zone operation, verify that 24 VAC transformer is 40 VA minimum.

does not open in

 

• Check all wiring connections between dampers and control board.

 

 

INSTALLER TEST mode..

 

 

 

 

• Verify the normally closed dampers are in the Primary Zone ductwork and the normally open

 

 

 

 

dampers are in the Secondary Zone ductwork..

 

 

 

 

 

 

 

 

 

The ventilation damper

Cycle time has been

• The damper will not open if the Ventilation Time has already been met.

 

 

does not open when the

met..

 

 

 

 

HVAC fan is active..

 

 

 

 

 

ODT error or outdoor air

• Check that the ODT is wired correctly to the

 

 

 

 

Outdoor

Resistance

 

 

outside of ODT range..

dehumidifier control board and connections are secure..

Temperature

 

 

 

 

 

 

• Check that the ODT is installed in the outdoor air

0°F

84,500 Ohms

 

 

 

intake according to the set-up specified in the

 

 

 

 

 

20°F

46,000 Ohms

 

 

 

Ventilation Section beginning on page 19..

 

 

 

 

 

 

 

 

40°F

26,000 Ohms

 

 

 

• Remove the ODT leads from the dehumidifier control

 

 

 

 

 

 

 

 

60°F

15,500 Ohms

 

 

 

board and check the resistance.. Compare the reading

 

 

 

with the table shown..

80°F

9,500 Ohms

 

 

 

 

100°F

6,000 Ohms

 

 

 

 

 

 

 

 

 

 

 

 

 

Dehumidifier is not

Drain line blocked or unit

• Verify that the unit is level.

 

 

 

draining properly..

not level..

• Check the drain line blockages and for a continuous downward slope.

 

 

 

 

 

 

 

 

The HVAC fan turns on

Dehumidifier is sampling

• The dehumidifier will turn on the HVAC fan during air sampling or as needed to meet the ventilation

unexpectedly..

or ventilation in

time..

 

 

 

 

progress..

 

 

 

 

 

 

 

 

 

 

Dehumidifier is

Normal function..

• Air is reheated across the condenser coil, resulting in a temperature rise between inlet and outlet.

producing hot air..

 

 

 

 

 

 

 

 

 

 

 