Aprilaire 1850 Determine Ventilation Requirements, Calculating Airflow Requirement, CFM Required

Models: 1830 1850w 1850

1 28
Download 28 pages 44.16 Kb
Page 21
Image 21
DETERMINE VENTILATION REQUIREMENTS

VENTILATION (continued)

DETERMINE VENTILATION REQUIREMENTS

CALCULATING AIRFLOW REQUIREMENT

1.The MINIMUM ventilation requirement is calculated using ASHRAE 62..2-2010..

ASHRAE Airflow in CFM = [House Area in Sq.. Ft.. x 0..01] + [(Number of Bedrooms +1) x 7..5]

NOTE: Use ‘Number of Bedrooms + 1’ or ‘Number of Occupants’, whichever is larger..

2.Table 1 shows the calculated airflow values to the nearest 5 CFM..

3.Record the required CFM.. ________

DETERMINE FRESH AIR DELIVERY RATE

Table 1 – CFM Required

House Sq. Ft.

 

Number of Bedrooms

 

2

3

4

5

6

 

 

 

 

 

 

 

1000

35

40

50

 

 

 

 

 

 

 

 

1500

40

45

55

60

70

 

 

 

 

 

 

2000

45

50

60

65

75

 

 

 

 

 

 

2500

50

55

65

70

80

 

 

 

 

 

 

3000

55

60

70

75

85

 

 

 

 

 

 

3500

 

 

75

80

90

 

 

 

 

 

 

1.Measure the negative static pressure of the return system at the location where the fresh air intake duct enters the return duct or dehumidifier inlet..

2See Table 2 for estimated inlet airflow in CFM, based on duct type, length and available negative pressure.. Use an airflow measuring device for a more accurate airflow delivery rate..

3. Record the delivered CFM.. ________

Table 2 – CFM Delivered

 

 

 

 

Negative Static Pressure (“w.c.) as Measured for Return Duct or Plenum

 

 

 

Duct Length

 

0.05

0.1

 

0.15

 

 

0.2

 

0.25

 

0.3

 

Flex

 

Pipe

Flex

Pipe

Flex

Pipe

Flex

 

Pipe

Flex

 

Pipe

Flex

 

Pipe

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10 ft.

60

 

65

85

 

90

105

 

110

120

 

125

135

 

140

150

 

160

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20 ft.

55

 

60

80

 

85

100

 

105

115

 

120

130

 

135

140

 

150

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

30 ft.

50

 

55

75

 

80

95

 

100

110

 

115

125

 

130

130

 

140

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: For the table above, 6” flex duct is laid loose with two, wide 90° bends and a fully opened damper. Rigid pipe values are based on 6” duct, two 90° elbows, and a fully open damper.. In both cases, the air intake is through a metal vent hood with inlet screen.. Airflow may need to be adjusted up or down for variations in duct work..

DETERMINE CYCLE TIME

1.Use the Required CFM and Delivered CFM from the above steps to determine the Cycle Time from Table 3..

2.The values highlighted in gray cannot be set due to the maximum 60 minute Cycle Time.. A second ventilation device (i..e.., bigger duct or second duct) will be required to meet ventilation needs..

21

Page 21
Image 21
Aprilaire 1850 Determine Ventilation Requirements, Calculating Airflow Requirement, Determine Fresh Air Delivery Rate