DUCTING FOR TWO ZONE INSTALLATIONS

In this installation the dehumidifier controls the humidity in two separate zones, a Primary and Secondary Zone.. The dehumidifier will dehumidify the Primary Zone as the first priority, and will switch to the Secondary Zone after the dehumidification needs of the Primary Zone have been satisfied..

IMPORTANT: Normally Closed dampers must be installed in the ducts serving the Primary Zone and Normally Open dampers installed in the ducts serving the Secondary Zone.

Required Components

10” Ductwork and Fittings Grilles with 10” Duct Collars Drain Line

2 – Aprilaire Model 6510, 10” Normally Closed Damper

2 – Aprilaire Model 6610, 10” Normally Open Damper

24 VAC Transformer (40VA min..) for Dampers

NOTE: 5442 Basement Kit includes 2 – 6510 Dampers,

2 – 6610 Dampers and a 24VAC (40VA) transformer

FIGURE 18 – Whole-Home Primary Zone Installation

TO/FROM

SUPPLY DUCT

PRIMARY ZONE

 

RETURN DUCT

NORMALLY CLOSED

DAMPERS

SUPPLY TO

6 ftSECONDARY ZONE MIN

RETURN FROM

SECONDARY ZONE

NORMALLY OPEN DAMPER

NORMALLY OPEN DAMPER

 

 

 

90-1875

FIGURE 19 – Whole-Home Secondary Zone Installation

 

 

 

 

TO /FROM

SUPPLY DUCT

 

 

 

 

 

SECONDARY ZONE

 

 

RETURN

 

NORMALLY

 

DUCT

 

OPEN

 

 

 

DAMPER

 

NORMALLY

 

SUPPLY TO

RETURN FROM

OPEN

 

PRIMARY ZONE

PRIMARY ZONE

DAMPER

 

 

 

 

 

 

 

 

NORMALLY CLOSED DAMPER

NORMALLY CLOSED DAMPER

 

 

 

 

 

90-1895

12

 

 

 

Page 12
Image 12
Aprilaire 1850w, 1830 installation instructions Ducting for TWO Zone Installations, Whole-Home Primary Zone Installation