TROUBLESHOOTING (continued)

TABLE 4 – Diagnostic Codes (continued)

Diagnostic

Code

Failure Mode

Action

Reset

E7

Float Switch Open

1.

Empty the condensate pan..

 

 

 

Self-Correcting

 

 

2.

Check the float switch connection at the control board..

 

 

 

 

 

 

3.

If not using a float switch, verify jumper is between float switch terminals on dehumidifier

 

 

 

 

control board..

 

 

 

 

 

 

4.

If the problem persists, replace the float switch..

 

 

 

 

 

 

 

 

 

 

 

 

E8

Inlet Air Temperature

1.

Verify all ductwork is properly sealed..

 

 

 

Self-Correcting

 

Out of 50°F – 104°F

2.

If no signs of leak points, contact Technical Support..

 

 

 

 

 

or dew point below

 

 

 

 

 

 

 

40°F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E9

Outdoor Temperature

1.

Check the sensor connection at the power board..

 

 

 

Self-Correcting

Outdoor

Resistance

 

 

Sensor Open or

2. Remove the wires from the terminals and measure

Temperature

 

 

 

 

 

 

 

Shorted

 

the resistance.. A short circuit will have a resistance

 

 

 

 

 

 

0°F

84,500 Ohms

 

 

 

 

 

very close to 0 Ohms and an open circuit will have

 

 

 

 

 

 

 

20°F

46,000 Ohms

 

 

 

 

 

a very very high resistance.. The table at right can

 

 

 

 

 

 

 

 

 

 

 

 

40°F

26,000 Ohms

 

 

 

 

 

be used to approximate the resistance based on

 

 

 

 

 

 

 

 

 

 

 

 

outdoor temperature..

60°F

15,500 Ohms

 

 

 

 

3.

If the sensor is not reading correctly, replace the

80°F

9,500 Ohms

 

 

 

 

 

sensor, Part No.. 8052..

 

 

 

 

 

 

 

100°F

6,000 Ohms

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

25

Page 25
Image 25
Aprilaire 1850w, 1830 installation instructions Troubleshooting