Aprilaire 1850w, 1830 Hard Wiring, Model 1850W, Voltage, Minimum Circuit Capacity

Models: 1830 1850w 1850

1 28
Download 28 pages 44.16 Kb
Page 6
Image 6
HARD WIRING

HARD WIRING

Model 1830 WARNING

ELECTRICAL SHOCK HAZARD: 115-volts may cause serious injury or death from electrical shock. Disconnect and tag electrical service before starting installation or field-service. Leave electrical service disconnected until installation or field-service is complete.

ELECTRICAL SHOCK HAZARD: An interrupted or broken ground may cause property damage, serious injury or death should an electrical fault occur. The cabinet must be grounded in accordance with NEC ANSI/NFPA 70-2011 or local codes. In Canada, refer to Canadian Electrical Code CSA C22.1.

FIRE HAZARD: Use of improper wire may cause serious injury, property damage or death due to fire. Do not use aluminum wire for electrical service to the dehumidifier. Use only copper wire.

Model 1850W CAUTION

Use of an undersized circuit breaker may cause property damage and/or the need for mold remediation service. See Specifications for wire and circuit breaker sizing.

The Model 1830 dehumidifier can be modified for applications where hard wire power to 115VAC is required; the Model 1850W must be hard wired.. An electrical disconnect switch can be installed as needed to comply with appropriate codes or ordinances.. The ON/OFF switch on the dehumidifier interrupts the 115VAC service to the internal components of the dehumidifier, but does not disconnect the power supply at the 115VAC terminals on the dehumidifier..

United States Installations: Make all electrical connections in accordance with the current edition of the NEC ANSI/NFPA 70 and any local codes or ordinances that may apply..

Canada Installations: Make all electrical connections in accordance with the current edition of the Canadian Electrical Code CSA C22..1 and any local codes or ordinances that may apply..

ELECTRICAL SPECIFICATIONS FOR HARD WIRING MODEL 1830 & 1850W

 

Model 1830

Model 1850W

 

 

 

Voltage

110-120 VAC, 60 Hz, 1 phase

110-120 VAC, 60 Hz, 1 phase

 

 

 

Minimum Circuit Capacity

9A

12A

 

 

 

Maximum Fuse or Circuit Breaker Amps

16A

20A

 

 

 

Minimum Wire Size AWG

14

14

 

 

 

6

Page 6
Image 6
Aprilaire 1850w Hard Wiring, Model 1850W, Voltage, Minimum Circuit Capacity, Maximum Fuse or Circuit Breaker Amps