ATT-TP-76450, Issue 9

As an exception, there are some new network elements that employ high DC current demands that when collectively configured in a packaged bay arrangement may exceed available fuse position capacities found at the BDFB. In a method to utilize the existing AT&T - DC distribution architecture, these individual network elements may be independently and directly fused at the BDFB via an SPDU. In these instances, direct feeds to the BDFB may be considered appropriate. However, the individual network element shall include an on/off /power cut off to locally disconnect the power from the bay components. In applications where a bay mounted SPDU is desired, AT&T has approved products designed to serve in that capacity and still allow

for independently fused services.