Common Systems Connection Standards | AT&T Services, Inc |
Date: August 31, 2007 |
2.1.3 Battery Return Conductor
2.1.3.1Each power feeder shall have its own battery return conductor. This design concept shall also carry through directly to each piece of equipment.
2.1.3.2Equipment configured with the battery return and chassis ground bonded together shall not be deployed in the network.
2.1.3.3Battery return and current path information must be provided in the supplier's response documentation to be in compliance with this item. List 1, 1X, 2 and 2X drains shall be provided in the documentation.
Drain Definitions
Defined below are the four drain categories used in this document.
•List 1 Drain:
Represents the average
•List 1X Drain
The amperage that will flow in one side of
a dual powered circuit when the other supply circuit has failed and the power plant feeding the remaining circuit is at it’s nominal operating voltage (float voltage).
•List 2 Drain:
Representing the peak current required to operate equipment at
•List 2X Drain
The amperage that will flow in one side of a dual powered circuit if the other supply circuit is failed and the power plant feeding the remaining circuit is at 42.64 volts or the total wattage divided by 42.64volts.
2.1.4Architecture Integration
Any equipment that requires more than a 70 amp fuse ( 56 amp load of List 2X ) may necessitate special accommodations.
2.2POWER TERMINATIONS AT THE NETWORK ELEMENT
Copyright ©2004 – 2006, AT&T Knowledge Ventures
All rights reserved
Page 6