5.13 Maximum optical power levels
Optical aggregate power level must not exceed +16.8 dBm optical power level at any connector (Hazard Level 3b). If the product exceeds this, there must be an embedded (to the network equipment) solution to protect the human exposure for both TXMT and RCV including the Automatic Power Reduction (APR) potential solutions.
5.14 Passive Network Element WDM Modules to be placed in the FDF
Passive Network Element WDM Modules (fiber optic splitters) to be placed in the FDF shall be standard LGX style vertical 12 slot Miscellaneous Panels (other types will not fit in the FDF).
5.15 Fiber Frames/Bays & Panels for all Network Elements
Fiber Frames/Bays & Panels for all Network Elements shall be Generation I, II, III Fiber Distribution Frames per
5.16 Fiber Raceway
Fiber raceways shall be standard trough system for all Interbay fiber jumper routing per GR-
6 Copper
6.1
6.2 Alternative
For Network Elements that require a unique connector
6.3 Coaxial Stripping Tools and Coaxial Crimping Tools
Coaxial Cable Stripping Tools and Coaxial Connector Crimping Tools shall be 734C/735C and hall be limited to those specific tools that each connector manufacturer approves for stripping and crimping.