Studer Innotec
40
Limit the time of activation {1512} {1513} Maximum duration of activation {1514} {1515}
When the conditions are met, either one or two relays are activated permanently. If you wish that
the activation duration is limited in time, even if the conditions are met, you can activate this
function. Once the relay is activated, a countdown runs according to the duration you have
selected. Once this countdown is completed the relay is released, even if the conditions are still
there. The relay can not be anymore activated as long as the activation conditions have not disap-
peared.
Temporal restrictions {1203} {1312}
These configurations allow the time frame to be defined in which the contact should under no
circumstances be activated. Three distinct schedules are accessible in the form of restriction
programs (programs 1 to 3). For each program, it is possible to select the day of the week where
the restriction is activated. If the day is selected it appears on the screen and if it is not selected it is
represented on the screen by two horizontal lines.
Once the days are selected, it is necessary to adjust the time frame where the restriction is active
using the “starting time” and “finishing time” configurations. If the finishing time is programmed
before the starting time, the restriction time frame is not taken into account. Below are the
configurations with their references:
Program 1 {1204} {1313}
o Days of the week {1205} {1314}
o Starting time {1206} {1315}
o Finishing time {1207} {1316}
Program 2 {1208} {1317}
o Days of the week {1209} {1318}
o Starting time {1210} {1319}
o Finishing time {1211} {1320}
Program 3 {1212} {1321}
o Days of the week {1213} {1322}
o Starting time {1214} {1323}
o Finishing time {1215} {1324}
If your installer has made additional adjustments, it is possible that the restrictions
could be active even if they do not appear in one of the three programs available
to you.
Contacts activated by an event {1455} {1456}
The auxiliary contacts may be activated by the states or events occurring in the installation. Each
event may be combined with another to establish complex functions.
Xtender OFF {1225} {1333}
The contact is activated if the Xtender inverter/charger is switched off, either following a fault or
manually.
Battery undervoltage alarm {1226} {1334}
If the undervoltage threshold is reached, this activates the contact. In contrast to the acoustic
alarm that is deactivated after a set time, this signal remains active as long as the battery voltage is
below the threshold. If the undervoltage fault cuts in, this condition remains active as does the
contact.
Battery overvoltage {1227) {1335}
Activates the contact in the event of battery overvoltage.