Inverter or smart boost overload {1228} {1336}
Activates the contact in the event of an error due to excessive power in the inverter or the Smart
Boost function. In the event that the inverter disconnects due to excess power and it is attempting
to restart, the contact is not activated until the end of the attempts.
Overtemperature {1229} {1337}
Activates the contact in the event of overtemperature in the electronics or the transformer.
No Overtemperature alarm {1520} {1521}
Activates the auxiliary contact if the charger function is active. When the function Smart-Boost is
running, the condition is not met to activate the contact.
Active charger {1231} {1339}
Activates the auxiliary contact if the charger function is active. When the smart boost function is
operating, the condition for activating the contact is not fulfilled.
Active inverter {1232} {1340}
Activates the auxiliary contact if the inverter function is active.
Smart boost active {1233} {1341}
Activates the auxiliary contact if the smart boost function is active. For more information on the
smart boost function, refer to the manual for the Xtender inverter/charger .
AC In present with fault {1234} {1342}
Activates the auxiliary contact if there is voltage present at the AC In input but this voltage does
not fulfil the conditions for activating the transfer relay.
AC In present {1235} {1343}
Activates the auxiliary contact if a voltage is present at the AC In input. This condition is
independent of the state of the transfer relay.
Transfer relay drawn {1236} {1344}
Activates the auxiliary contact if the transfer relay is drawn.
AC Out present {1237} {1345}
Activates the auxiliary contact if a voltage is present at the output of the Xtender inverter/charger.
Battery charging in bulk charge phase {1238} {1346}
Activate the auxiliary contact if the battery is in bulk charge phase.
Battery charging in absorption phase {1239} {1347}
Activates the auxiliary contact if the battery is in absorption phase. If the periodic extended
absorption function is activated, the contact is also activated in this phase.
Battery charging in equalization phase {1240} {1348}
Activates the auxiliary contact if the battery is in equalization phase.
Battery charging in floating phase {1242} {1350}
Activates the auxiliary contact if the battery is in maintenance phase. If the extended reduced
floating function is activated, the contact is also activated in this phase.
Contacts activated by the battery voltage {1245} {1353}
These configurations allow activation of the auxiliary contacts if the battery voltage passes below a
selected voltage during a period that is configurable as well. Three voltages linked to three
durations are configurable to activate the auxiliary contact.