CONNECTION

The RCC-02 remote control must be firmly fastened using 3 screws on a flat support. The remote
control RCC-03 is meant to be integrated. It must be mounted by means of 4 screws (not supplied)
on a flat place without any mechanical constraints to the front plate. Once the RCC remote
control is fastened it can be connected to the inverter using the authorised cable only. If the cable
is damaged or if a socket is detached, the cable must not be connected since this can cause the
whole installation to malfunction.
A maximum of 3 remote controls can be connected to one unit.
SERIES CONNECTION
To connect several RCC remote controls in series, you must activate termination at the two
extremities on both units and deactivate it on the intermediate units.
Termination is activated on each Studer Innotec product by default.
Activate the termination on each element of the series connection with a single cable.
Deactivate the termination on each element of the series connection with two cables.
To deactivate the termination on an inverter or RCC remote control, turn the switch to the right.
RCC-02 termination activated (position T)
RCC-02 termination deactivated (position O)
RCC-03 termination activated
(left position)
RCC-03 termination deactivated
(right position)
To activate the termination on the Xtender,
move the two mini-switches to position T, and
to deactivate it, move them downwards to
position O.