CyberChiller Series Installation, Operation & Maintenance Manual
2.5Piping Connections
2.5.1Process Supply Fluid Lines
Coolant fluid supply and return lines are connected from the equipment being cooled to the CyberChiller via copper sweat fittings provided in the pump section.
2.5.2Refrigerant
2.5.2.1Split Air Cooled Systems
Split
Split systems coupled with a remote condensing unit will require a copper discharge and a copper liquid line.
All refrigeration piping should be installed with high temperature soldered joints. Use standard refrigeration practices for piping supports, leak testing, dehydration and charging of the refrigeration circuits. The refrigeration piping should be isolated from the building by the use of vibration isolating supports. To prevent tube damage when sealing openings in walls and to reduce vibration transmission, use a soft flexible material to pack around the tubes.
Clear all pipe connections of debris and prepare the connections for soldering. Use only "L" or "K" grade refrigerant copper piping. Be careful not to allow solder/piping debris to get inside refrigerant lines. Silver solder containing a minimum of 15% silver is recommended. Dry nitrogen should be flowing through the tubing while soldering at a rate of not less than
Refrigerant lines for split systems must be sized according to the piping distance between the evaporator and the condenser. Each valve, fitting and bend in the refrigerant line must be considered in this calcula- tion. Refer to the following charts for standard equivalent lengths, in feet, of straight pipe.
Oil traps must be included in the discharge line every 20 feet in the vertical risers and the refrigerant lines must be sloped ¼ inch for every 10 feet in the horizontal lines to ensure proper oil return to the compressor. An inverted trap is required on the discharge line of the remote condenser to help prevent oil and liquid from flooding back to the compressor.
|
|
| PRESSURE |
|
|
|
|
|
|
|
| RELIEF VALVE |
|
|
|
|
|
INTERCONNECTING | (OPTIONAL) |
|
|
|
|
| ||
SEE NOTE 2 |
|
|
|
|
| |||
FIELD PIPING BY OTHERS |
|
|
|
|
|
| ||
|
|
|
|
| SIGHT GLASS | LIQUID LINE | EXPANSION | |
|
|
|
|
| DRIER/STRAINER |
| SOLENOID VALVE | VALVE |
|
|
|
|
|
|
| ||
|
|
|
| SERVICE |
|
|
|
|
|
|
| RECEIVER | PORT |
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| |
|
|
|
|
| HOT GAS |
| ELECTRONIC |
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
| ||
|
|
|
|
|
|
| ||
|
|
|
|
|
|
| ||
|
|
|
|
| HOT GAS BYPASS |
| ||
|
|
|
|
| SOLENOID VALVE |
| ||
|
|
|
|
|
| VALVE |
| |
|
|
|
|
|
|
| LINE | |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| |
|
|
| SCHRADER CHECK | ROTOLOCK |
|
| EQUALIZER | |
|
|
|
|
| ||||
|
|
|
|
|
|
|
| |
|
|
|
|
| VALVE |
|
|
|
CONDENSER |
|
|
|
|
|
| ||
FAN SPEED CS |
|
|
|
| ROTOLOCK |
| ||
CONTROL |
|
|
|
|
| |||
|
|
|
|
|
| |||
INTERCONNECTING |
| HIGH PRESSURE | HP |
|
|
| ||
FIELD PIPING BY OTHERS |
| LIMIT SWITCH |
|
|
| |||
|
|
|
|
| ||||
|
|
|
| SERVICE PORT |
| OW PRESSURE | ||
|
|
|
|
|
|
| IMIT SWITCH |
NOTES:
SERVICE PORT
1) LOCATE AUTOMATIC AIR VENT AT HIGHEST POINT OF SYSTEM.
2) PRESSURE RELIEF VALVE MUST BE PIPED TO EXIT THE CABINET.
INLET
EVAP
OUTLET
Figure 3- Typical Piping Air Cooled System
|
|
| (©October, 2006) | |
|
|
|
|
|
|
|
|
|
|