CyberChiller Series Installation, Operation & Maintenance Manual
SYMPTOM | PROBABLE CAUSE | RECOMMENDATION |
|
|
|
Head Pressure is too Low a. Loss of refrigerant (indicated by bubbles in the sight glass).
Repair leak and recharge system.
Suction Pressure too Low | a. Expansion valve stuck in the open | Repair or replace valve. |
| position (indicated by abnormally cold |
|
| suction line). |
|
| b. Low charge, flash gas in liquid line | Repair leak and recharge system. |
| (indicated by bubbles in sight glass). |
|
| c. Clogged drier/strainer (feels cool to | Replace drier/strainer. |
| the touch). |
|
| d. Obstructed expansion valve (indicat | Replace valve. |
| ed by loss of capacity). |
|
| e. Loss of control fluid from expansion | Replace valve or control head. |
| valve control head (indicated by |
|
| bubbles in the sight glass). |
|
|
|
|
Compressor Fails to Start | a. Temperature setpoint too high. | Adjust to desired temperature. |
| b. Compressor internal protector | Check compressor for short circuit or |
| is open. | ground. |
| c. Complete loss of refrigerant charge | Locate and repair leak. Recharge |
| (low pressure safety switch). | system. |
| d. Condenser pressure too high (high | Check condenser for obstructions. |
| pressure safety switch). |
|
| e. Minimum off time has not expired. | Wait for time to expire. |
System Short of Capacity a. Low refrigerant (indicated by bubbles in sight glass).
b. Expansion valve stuck or obstructed (short cycling or continuous running).
c. Clogged drier/strainer (feels cold).
Check for leaks Repair and recharge system.
Remove valve and clear obstruction or replace valve.
Replace with new drier/ strainer.
Compressor Short Cycles a. Low line voltage causing | Check power source for cause of low |
compressor to overheat. | line voltage. |
b. Reduced flow rate. | Check pump and strainer. |
c. Lack of refrigerant | Check for leak. Repair and recharge |
| system. |