CyberChiller Series Installation, Operation & Maintenance Manual
CAUTION
POE oil is used in systems with
PREPARING SYSTEM FOR CHARGING
1.With all the system piping connections made, perform a dry nitrogen leak detection test on the system. Using dry nitrogen only, pressurize the system to 150 psig. Since there is no refrigerant in the system to detect, leaks may be detected by observing the standing pressure.
2.After ensuring there are no leaks, evacuate the system to 50 microns and hold the vacuum for 2 hours.
3.Break the vacuum by supplying
FINE TUNING THE SYSTEM CHARGE
4.Disconnect the refrigerant cylinder from the discharge side of the compressor and connect it to the suction side.
5.Start the system and use the microprocessor controller to lower the supply water temperature setpoint
6.Allow the discharge pressure to rise to
condenser (or reduce the water glycol flow), to raise the pressure.
7.Slowly meter
CAUTION
Add liquid refrigerant slowly to prevent the refrigerant oil from “washing out” of the compressor.
8.While monitoring the sight glass, take a sub- cooling temperature reading on the output side of the condenser. The
9.If necessary, add liquid refrigerant to maintain adequate
10.Take a superheat reading on the suction line 6" from the compressor. The superheat should be 12- 20°F.
2.7.5High/Low Pressure Limit Switch
CyberChiller units utilizing thermal expansion valves are equipped with hermetically sealed
The Low pressure switch will open the control circuit to the microprocessor digital input to disengage power to the compressor contactor if suction pressure drops below a specific pressure. The microprocessor will ignore the absence of this signal during the cold start delay period after starting of a compressor. Should this signal continue to be absent or open after the cold start period, the affected compressor will be shut down with an alarm indication at the controller. The
(©October, 2006) | ||||
|
|
|
|
|
|
|
|
|
|