Wiring Tables
Heat Pump
Terminal |
| Device |
|
|
|
| 1H1C |
|
| 2H1C |
|
|
| 3H1C | 2H2C |
| 3H2C |
|
| 4H2C |
| 3H3C | |||||
TH |
|
| Console |
|
|
| Connect the console between the TH terminals (no polarity) |
|
|
|
|
|
| ||||||||||||||
TH |
|
|
|
|
|
|
|
|
|
|
| ||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
PS |
|
| Plenum sensor |
| Connect the plenum sensor between the PS and CS terminals (no polarity) |
|
|
| |||||||||||||||||||
CS |
|
| Common S |
|
|
| Common terminal for the plenum sensor and the outdoor sensor |
|
|
|
|
|
| ||||||||||||||
OS |
|
| Outdoor sensor |
| Connect the outdoor sensor between the CS and OS terminals (no polarity) |
|
|
| |||||||||||||||||||
DE |
|
| Dual Energy |
|
|
| Connect the |
|
|
| |||||||||||||||||
CC |
|
| Common C |
|
|
| Common terminal for the |
|
|
| |||||||||||||||||
UN |
|
| Unoccupied mode input |
| Connect a dry contact between the UN and CC terminals (no polarity) |
|
|
|
| ||||||||||||||||||
H |
|
| Humidifier (24 Vac / 1 A) |
| Connect the humidifier between the H terminals (dry contact) |
|
|
|
|
|
| ||||||||||||||||
H |
|
|
|
|
|
|
|
|
| ||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
D |
|
| Dehumidifier (24 Vac / 1 A) |
| Connect the dehumidifier between the D terminals (dry contact) |
|
|
|
|
|
| ||||||||||||||||
D |
|
|
|
|
|
|
|
|
| ||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
R |
|
| Power (24 Vac) |
|
| √ |
|
| √ |
|
|
|
| √ | √ |
|
| √ |
|
| √ |
|
| √ | |||
C |
|
|
|
| √ |
|
| √ |
|
|
|
| √ | √ |
|
| √ |
|
| √ |
|
| √ | ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||
Y1 |
|
| Compressor 1 (24 Vac / 1 A) |
|
| √ |
|
| √ |
|
|
|
| √ | √ |
|
| √ |
|
| √ |
|
| √ | |||
Y2 |
|
| Compressor 2 (24 Vac / 1 A) |
|
|
|
|
|
|
|
|
|
|
| √ |
|
| √ |
|
| √ |
|
| √ | |||
Y3 |
|
| Compressor 3 (24 Vac / 1 A) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| √ | |||
W1 |
|
| Auxiliary heat 1 (24 Vac / 1 A) |
|
|
|
|
| √ |
|
|
|
| √ |
|
|
| √ |
|
| √ |
|
|
| |||
W2 |
|
| Auxiliary heat 2 (24 Vac / 1 A) |
|
|
|
|
|
|
|
|
|
| √ |
|
|
|
|
|
| √ |
|
|
| |||
W3/O/B |
| Reversing valve (24 Vac / 1 A) |
|
| √ |
|
| √ |
|
|
|
| √ | √ |
|
| √ |
|
| √ |
|
| √ | ||||
G |
|
| Fan (24 Vac / 1A) |
|
| √ |
|
| √ |
|
|
|
| √ | √ |
|
| √ |
|
| √ |
|
| √ | |||
L |
|
| Fault (24 Vac / 5 mA) |
|
| √ |
|
| √ |
|
|
|
| √ | √ |
|
| √ |
|
| √ |
|
| √ | |||
WW |
|
| Defrost (24 Vac / 5 mA) |
|
| √ |
|
| √ |
|
|
|
| √ | √ |
|
| √ |
|
| √ |
|
| √ | |||
NC |
|
|
|
|
|
|
|
|
|
|
|
| Not used |
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| HVAC |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Terminal |
|
| Device |
| 1H |
| 2H |
| 3H | 1C | 2C |
|
| 3C |
| 1H1C | 1H2C | 2H1C | 2H2C | 2H3C | 3H1C | 3H2C | 3H3C | ||||
TH |
|
| Console |
| Connect the console sensor between the TH terminals (no polarity) |
|
|
|
|
|
|
| |||||||||||||||
TH |
|
|
|
|
|
|
|
|
|
| |||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
PS |
|
| Plenum sensor |
| Connect the plenum sensor between the PS and CS terminals (no polarity) |
|
|
|
|
|
| ||||||||||||||||
CS |
|
| Common S |
| Common terminal for both plenum sensor and outdoor sensor |
|
|
|
|
|
|
|
|
| |||||||||||||
OS |
|
| Outdoor sensor |
| Connect the outdoor sensor between the OS and CS terminals (no polarity) |
|
|
|
|
|
| ||||||||||||||||
DE |
|
|
|
|
|
|
|
|
|
|
| Not used |
|
|
|
|
|
|
|
|
|
|
|
| |||
CC |
|
| Common C |
| Common terminal for the unoccupied mode input |
|
|
|
|
|
|
|
|
|
| ||||||||||||
UN |
| Unoccupied mode input | Connect a dry contact between UN and R terminals (no polarity) |
|
|
|
|
|
|
|
|
| |||||||||||||||
H |
| Humidifier (24 Vac / 1 A) | Connect the humidifier between the H terminals (dry contact) |
|
|
|
|
|
|
|
|
| |||||||||||||||
H |
|
|
|
|
|
|
|
|
|
| |||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
D | Dehumidifier (24 Vac / 1 A) | Connect the dehumidifier between the D terminals (dry contact) |
|
|
|
|
|
|
|
|
| ||||||||||||||||
D |
|
|
|
|
|
|
|
|
| ||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
R |
|
| Power (24 Vac) |
| √ |
| √ |
| √ | √ | √ |
|
| √ |
| √ | √ | √ | √ | √ | √ |
| √ | √ | |||
C |
|
|
| √ |
| √ |
| √ | √ | √ |
|
| √ |
| √ | √ | √ | √ | √ | √ |
| √ | √ | ||||
|
|
|
|
|
|
|
|
|
| ||||||||||||||||||
Y1 | Cooling unit 1 (24 Vac / 1 A) |
|
|
|
|
|
| √ | √ |
|
| √ |
| √ | √ | √ | √ | √ | √ |
| √ | √ | |||||
Y2 | Cooling unit 2 (24 Vac / 1 A) |
|
|
|
|
|
|
|
| √ |
|
| √ |
|
| √ |
|
| √ | √ |
|
| √ | √ | |||
Y3 | Cooling unit 3 (24 Vac / 1 A) |
|
|
|
|
|
|
|
|
|
|
| √ |
|
|
|
|
|
| √ |
|
|
| √ | |||
W1 | Heating unit 1 (24 Vac / 1 A) |
| √ |
| √ |
| √ |
|
|
|
|
|
|
| √ | √ | √ | √ | √ | √ |
| √ | √ | ||||
W2 | Heating unit 2 (24 Vac / 1 A) |
|
|
| √ |
| √ |
|
|
|
|
|
|
|
|
| √ | √ | √ | √ |
| √ | √ | ||||
W3/O/B | Heating unit 3 (24 Vac / 1 A) |
|
|
|
|
| √ |
|
|
|
|
|
|
|
|
|
|
|
|
|
| √ |
| √ | √ | ||
G |
|
| Fan (24 Vac / 1 A) |
| √ |
| √ |
| √ | √ | √ |
|
| √ |
| √ | √ | √ | √ | √ | √ |
| √ | √ | |||
L |
|
|
|
|
|
|
|
|
|
|
| Not used |
|
|
|
|
|
|
|
|
|
|
|
| |||
WW |
|
|
|
|
|
|
|
|
|
|
| Not used |
|
|
|
|
|
|
|
|
|
|
|
| |||
NC |
|
|
|
|
|
|
|
|
|
|
| Not used |
|
|
|
|
|
|
|
|
|
|
|
|
5/24/07 | 4/12 |