Section: Wire the Burner

Figure 11 - Typical Burner Sequence of Operation - 7505

 

 

1

Standby

9

Pump

 

 

 

 

 

 

 

Prime

 

 

 

 

 

 

 

 

 

2

 

3

 

 

4

 

Valve-on

Trial for

 

 

 

 

 

 

 

 

Lockout

 

Delay

 

 

 

Ignition

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

Ignition

Carryover

8

 

6

 

 

7

 

 

 

Motor-Off

 

 

 

 

 

 

Run

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Relight

 

 

Delay

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 4 - 7505 Flame Detection

Flame Detection Range

Normal = 0 to 1600 ohms

Limited = 1600 ohms to lockout

Cad Cell Resistance Measurement:

If the Beckett 7505 control is equipped with the GeniSys Display Module, part 52067U, the cad cell resistance can be selected and read on the LCD screen. Also, the GeniSys Contractor Tool, part 52082U, can be used for this purpose.

If these are not available, the cad cell leads can be unplugged from the control and the resistance measured with a meter in the conventional way. Conduct these tests with flame present.

Table 5 - 7505 Status Light Explanation Table

Light

On Continuously

Flashing

Color

 

 

Red

Restricted (Hard) Lockout

Soft Lockout

 

 

 

Green

Flame Sensed during normal

Recycle

 

operation (Could be stray light

 

 

during standby)

 

 

 

 

Yellow

Control is in Pump Prime mode

N/A

 

or Reset button currently held

 

 

for 15+ seconds.

 

 

 

 

Figure 12 - GeniSys 7505 Control with Optional Components

Reset Button

Wiring

Connections

with Red Light

 

Yellow Light

 

Green Light

 

Cad Cell

Connections

Thermostat Terminals

Communication Port 2

 

Communication Port 1

Optional Components:

Contractor’s Tool:

Hand-held device for

programming and diagnostics

Display Module: Permanent device for programming and diagnostics

Alarm Module:

For adding isolated low voltage alarm contacts to the base control. See Alarm Module Instructions for specifications.

CF2500/CF3500 Burner Manual

13

Page 13
Image 13
Beckett CF2500 manual Standby, Cad Cell Resistance Measurement