Figure 2 - Dimensions: Minimum Combustion Chamber and Air Tube Mounting.
* Install burner with 2° pitch as shown.
T
1/4” ± 1/8”
H D *2°
L
E
Firing Rate | Minimum Dimensions | ||
(gph) |
|
| |
H | L | ||
| |||
17 | 10.5” | 48.0” | |
22 | 11.5” | 58.0” | |
27 | 12.5” | 66.0” | |
32 | 12.5” | 73.0” | |
35 | 13.0” | 77.0” |
Air Tube Combination Codes
Model | Tube | Dimension | Dimension | Code | Dimension | |
T | D | E | ||||
|
|
| ||||
CF2500A/ CF2500 |
| CF 66 KP | ||||
KP | CF 102 KP | |||||
| ||||||
| CF 136 KP | |||||
|
| |||||
|
| CF 176 KP | ||||
|
| 8” | 8” | CF 80 KM | ||
|
| 8” | CF 92 KM | |||
CF3500 | KM | 8” | CF 114 KM | |||
| 15” | 8” | CF 150 KM | |||
|
| |||||
|
| 19” | 8” | CF 190 KM | ||
|
| CF 114 KR | ||||
| KR | 14” | CF 140 KR | |||
|
| 19” | CF 190 KR | |||
|
|
|
|
|
|
Verify Air Tube
The information in this section may be disregarded if the air tube is supplied by the appliance manufacturer.
The following tube arrangements are available –
○CF2500 - Tube KP
○CF2500A - Tube KP
○CF3500A - Tube KM
Maximum firing capacity depends on the firebox pressure. Use Table 2 to verify the correct air tube type for the firing rate required. (Tube KR [CF3500A] is an optional air tube combination for maximum capacity rate. It requires a larger I.D. flange Number 51631.)
See Figure 2 to verify the correct air tube length and air tube combination code.
Figure 3a - Firebox Pressure: CF2500A with no Reserve Air
U.S. GPH | 25 |
|
|
|
|
|
24 |
|
|
|
|
| |
Rate |
|
|
|
|
| |
|
|
| KP |
|
| |
Firing |
|
|
|
|
| |
23 |
|
|
|
|
| |
Maximum | 22 | 0.2 | 0.4 | 0.6 | 0.8 | 1.0 |
| 0.0 | |||||
|
| Firebox Pressure in Inches Water Column (W.C.) |
|
Figure 3b - Firebox Pressure: CF3500 with no Reserve Air
U.S. GPH | 35 |
|
|
|
|
|
30 |
|
|
|
|
| |
Firing Rate |
|
| KR |
|
| |
25 |
|
| KM |
|
| |
Maximum | 20 | 0.2 | 0.4 | 0.6 | 0.8 | 1.0 |
| 0.0 | |||||
|
| Firebox Pressure in Inches Water Column (W.C.) |
|
6