Section: General Information
General Information
Hazard Definitions
Indicates a hazardous situation which, if not
avoided, will result in death or serious injury.
Indicates a hazardous situation, which, if not
avoided, could result in death, or serious injury.
Used with the safety alert symbol, indicates a
hazardous situation, which, if not avoided, may result in minor or moderate injury.
Used to address practices not related to personal injury.
Specifications
Owner’s Responsibility:
Follow these instructions exactly.
Failure to follow these instructions, misuse, or incorrect adjustment of the burner could result in asphyxiation, explosion or fire.
Contact a professional, qualified service agency for the installation, adjustment and service of your oil burning system. Thereafter, have your equipment adjusted and inspected at least annually to ensure reliable operation. This work requires technical training, trade experience, licensing or certification in some states and the proper use of special combustion test instruments.
yNever store or use gasoline or other flammable liquids or vapors near this burner or appliance.
yNever attempt to burn garbage or refuse in this appliance.
yNever attempt to light the burner by throwing burning material into the appliance.
yNever attempt to burn any fuel not specified and approved for use in this burner.
yNever restrict the air inlet openings to the burner or the combustion air ventilation openings in the room.
Frozen Plumbing and
Water Damage Hazard
Fuels
Firing Range
Motor
Ignition Trans.
Housing
Fuel Unit
Oil Nozzle
Dimensions
U.S. #1 or #2 heating oil only (ASTM D396) Canada #1 stove oil or #2 furnace oil only
DO NOT USE
GASOLINE, CRANKCASE OIL, OR ANY OIL CONTAINING GASOLINE.
CF2500A - 17.0 to 19.9 gph
CF2500 - 17.0 to 25.0 gph
CF3500A - 17.0 to 35.0 gph
2 HP 3450 rpm 208/230/60 Hz Standard 13.4 amps @ 230 VAC
Optional Voltages:
208, 230, 480, 575
Continuous Duty, 120V/12,000V
Cast aluminum
100 to 300 psig
45o to 70o Solid
Refer to Figure 8.
If the facility is unattended in severely cold weather, burner primary control safety lockout, heating system component failures, power outages or other electrical system failures could result in frozen plumbing and water damage in a matter of hours. For protection, take preventive actions such as having a security system installed that operates during power outages, senses low temperature and initiates an effective action. Consult with your heating contractor or security agency.
Service Agency Responsibility:
Follow these instructions exactly.
Failure to follow these instructions could result in asphyxiation, explosion or fire.
yPlease read all instructions before proceeding. Follow all instructions completely.
yThis equipment must be installed, adjusted and started by a qualified service agency that is licensed and experienced with all applicable codes and ordinances and responsible for the installation and commission of the equipment.
yThe installation must comply with all local codes and ordinances having jurisdiction and the latest editions of the NFPA 31 and
50 Hz Motors - The burner ratings, air settings and nozzle ratings are based on standard 60 Hz motors (at 3450 rpm). Derate
all ratings 20% when using 50 Hz motors. Consult factory for specific application data.
High altitude installation - Accepted industry practice requires no derate
of burner capacity up to 2000 feet above sea level. For altitudes higher than 2000 feet, derate burner capacity 2% for each 1000 feet above sea level.
CF2500/CF3500 Burner Manual