Section:
Pre-installation Checklist
Combustion Air Supply
Adequate Combustion and
Ventilation Air Supply Required
Failure to provide adequate air supply could seriously affect the burner performance and result in damage to the equipment, asphyxiation, explosion or fire hazards.
yThe burner cannot properly burn the fuel if it is not supplied with a reliable combustion air source.
yFollow the guidelines in the latest editions of the NFPA 31 and
The burner requires combustion air and ventilation air for reliable operation. Assure that the building and/or combustion air openings comply with National Fire Protection Standard for
For appliance/burner units in confined spaces, the room must have an air opening near the top of the room plus one near the floor, each with a free area at least one square inch per 1,000 Btu/hr input of all fuel burning equipment in the room.
For other conditions, refer to the latest edition of NFPA 31 (CSA
If there is a risk of the space being under negative pressure or of exhaust fans or other devices depleting available air for combustion and ventilation, the appliance/ burner should be installed in an isolated room provided with outside combustion air.
Clearances
With the burner installed in the appliance, there must be adequate space in front of and on the sides of the burner to allow access and operation. Verify that the clearance dimensions comply with all local codes and with the appliance manufacturer’s recommendations.
Figure 1 – Typical Nameplate
Fuel Supply
Oil Supply Pressure
Control Required
Damage to the filter or pump seals could cause oil leakage and a fire hazard.
yThe oil supply inlet pressure to the burner cannot exceed 3 psig.
yInsure that a pressure limiting device is installed in accordance with the latest edition of NFPA 31.
yDo not install valves in return line.
yGravity Feed Systems: Always install an
The fuel supply piping and tank must provide #1 or #2 fuel oil at pressure or vacuum conditions suitable for the fuel unit (oil pump) on the burner. Refer to fuel unit literature in the literature envelope in the burner carton to verify allowable suction pressure.
If fuel supply is level with or higher than fuel unit —
○When the fuel unit is not required to lift the oil, the installation is usually suitable for either a
○The fuel unit is shipped with the
When fuel supply is below the burner fuel unit —
Use a
related problems during operation.
General Model Information
Serial Number, Including Date Code
Rating Information
Approval Agency Symbols
Primary Group and Fuel
Model “XX”
Series (Fuel) Burner
SERIAL NUMBER
050214-00000
Control Circ: 120V/60Hz 4.5A
Motor Circ: 120V/60Hz 4.0A
LISTED
(FUEL) BURNER NO.P100000
For use with Group 8 . . .
MFR’S SETTINGS
| X |
|
|
| R.W. Beckett Construction & | ||
| X |
|
|
| |||
| X |
|
|
|
|
| Setting Data |
|
|
|
|
|
| ||
| X |
|
|
| |||
| X |
|
|
|
| ||
| X |
|
|
|
| ||
|
|
|
|
|
|
| R.W. Beckett Specification |
|
|
|
|
|
|
| |
| XX000 R00 | ||||||
|
|
|
|
|
| Number and Revision | |
|
|
|
| ||||
|
|
|
|
|
|
| Boiler Manufacturer and |
|
|
|
|
|
|
| Model, When Applicable |
|
|
|
|
|
|
| Additional Codes |
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
MP 1192 XX000 R00
4