Page 30 | BRADFORD WHITE CORP. |
|
|
7.2.2 Filter
The filter used in the Brute Deluxe is washable with an 83% arrestance. Since the filter is washable, it will only need replacement when unwashable, deteriorated or damaged. If filter replacement is needed, it should only be replaced with a factory part. Inspect the air filter. If there is debris on the air filter, remove it from the filter box, and wash it with mild soap and water. Ensure that the filter is completely dry before re- installing, in reverse order.
7.2.3 Gas Valves
The gas valves are designed to operate with supply pressures of
To remove a valve, shut off
7.2.4 Manual Reset High Limit Control
The high limit switch is manual reset switch with an adjustable set point, up to 240°F (116°C) on boiler models and 200°F (93°C) on water heater models and boilers ordered with low temperature controls. To replace the switch, shut off the
7.2.5 Temperature Control
The temperature control is a Honeywell L6008. To replace the control, shut off the
7.2.6 IgnitionControls
The ignition controls ensure the proved interrupted- type ignition system. They control the hot surface ignitors and prove that the flame signal is appropriate for powering the gas valves. It also controls the blower’s
To replace a control, shut off the
7.2.7 Ignitors/Sensor
The ignitor/sensor used are 120v "hot surface" type. They are energized whenever there is a call for heat and switched off when ignition is established and flame has been sensed. Brute Deluxe sizes 500 and 750 have one ignitor/sensor. Sizes 1000 to 2000 have two ignitor/sensors. To replace the ignitor/sensor, shut off the
Caution
Ignitor gets hot.
7.2.8 Transformer
The transformer is not capable of supplying control voltage for external devices such as zone valves, which must have their own separate power supply. Should a transformer need replacing, shut off the
7.2.9 Blowers
The combustion air blowers bring the combustion air for the Brute Deluxe from the upper chamber to the lower chamber. Mixing of the gas and air occurs in the burners. Sizes 500, 750 and 1000 each have one blower, and sizes 1250 to 2000 each have two blowers. If a blower change is required, turn off the
7.2.10 Flow Switch
The Brute Deluxe uses a
7.2.11 Heat Exchanger Coil
WARNING
Black carbon soot buildup on a dirty heat exchanger can be ignited by a random spark or flame, thereby creating a risk of fire or explosion.. To prevent this from happening, dampen the soot deposits with a wet brush or fine water spray before servicing the heat exchanger.