1Thermostat callsfor heat.
The relay closes on the thermostat board, sending 24 volts from the “COM” terminal of the thermostat board
to the flue damper.
2Flue damper begins to rotate open. Oncedamper is full open, 24 volts is allowed to continue through damper to the
TH”terminal of ignition module.
3LED on ignition module illuminates.
4
5Once pilotflame is proven, sparking will stop.
Page 4
Sequence of Operation
Trial for ignition (90second trials, 3 trials with 30 second pause between trials).
Ignitionmodule simultaneously sends:
1. 24 volts from “MV/PV” terminal, to “MV/PV”
terminal of gas valve (common terminal).
2. 24 volts from “PV” terminal, through the
ECO located in the lower thermister, to “PV”
terminal of gas valve to establish
gas flowat pilot.
3. Low current high voltage from “spark”
terminal, to generate spark at the pilot and
ignite pilot gas flow.
4. Pilot flame proving signal (measured in
micro-amps). fromthe “sense” terminal, to
prove pilotflame.
6Once sparking stops, 24 volts is sent from“MV” terminal on
module, to “MV” terminal on gas valve to establish main
burnergas flow. Main burners ignite from the pilot flame.
The ignition module constantlymonitors pilot flame. If pilot
flame is lost, pilot and main burner are shut down. After a
30 second purge period, module willattempt to re-light pilot
beginning at sequence4 above.
7Main burner fires until the thermostat is satisfied. The relay on
the thermostat board opens, interrupting 24 volts through the
damper and ignition module.Pilot and main burner is turned off.
8Flue damper rotates to the closed position.
WIRING DIAGRAM
LOCKOUT CONDITION
Ignition module will “lockout” if the pilot can not be lit after 3
ignition trials. The ignition module indicates a lockout condition
by the continues flash of the LED located on the module.
Lockout reset is accomplished by interrupting 120 VAC to the
unit for at least 5 seconds.
4