Bradford-White Corp Flammable Vapor Ignition Risistant Water Heaters LED Status, Control Status

Models: Flammable Vapor Ignition Risistant Water Heaters

1 40
Download 40 pages 15.97 Kb
Page 5
Image 5
Honeywell Gas Control Troubleshooting Chart

Honeywell Gas Control Troubleshooting Chart

Flammable Vapor Ignition Resistant Water Heaters

Observe green LED indicator on Gas Control. Error flash codes are displayed with a three second pause before repeating. Check and repair the system as noted in the troubleshooting table below.

Green LED Indicator

LED Status

Control Status

 

 

 

Probable Cause

Service

Procedure

None (LED not on

or flashing

One flash and three second pause

LED on

continuously

(Solid)

Two flashes and

three second

pause

Gas Control is operating normally. Pilot flame may not be present. Check for pilot flame through sight glass and light if necessary.

If set point knob is in “PILOT” position then pilot flame is detected. Turn set point knob to desired setting.

Set point knob has been recently turned to the “OFF” position. Wait until LED goes out before attempting to relight

Weak pilot signal detected. System will reset when pilot flame is sufficient.

1.Gas Control is functioning normally.

2.Gas Control is not powered. Light pilot.

3.Thermopile failure.

Gas Control is powered and waiting for the set point knob to be turned to a water temperature setting.

Set point knob was turned to “OFF” position.

1.Thermopile failure

2.Unstable pilot

3.Pilot tube block or restricted.

4.Resettable thermal switch has opened

If the pilot will not stay lit replace pilot assembly. If problem persists replace Gas Control.

Normal operation. Adjust thermostat to desired temperature setting.

LED will go out and the control will function normally when the pilot is lit.

1.See service procedure RG-II

2.See service procedure RG-III

3.See service procedure RG-III

4.See service procedure RG-VIII

Three flashes and

Insufficient water heating. System

three second will reset. pause

Four flashes and

1.Temperature sensor out of calibration

1. Temperature sensor out of

1.See service procedure RG-VI

1. See service

three second

pause

Excessive tank temperature. System must be reset.

calibration

2. Faulty Gas Control

procedure RG-VI

2. See service

procedure RG-VI

5

55

Page 5
Image 5
Bradford-White Corp Flammable Vapor Ignition Risistant Water Heaters Honeywell Gas Control Troubleshooting Chart