Briggs & Stratton 01815-0, 01938-0 Fuel and Electrical Inlet Dimensions, Lifting the Generator

Models: 01815-0 01938-0

1 48
Download 48 pages 38.43 Kb
Page 5
Image 5
Fuel and Electrical Inlet Dimensions

Briggs & Stratton Power Products Home Generator

Installation Manual

Figure 1 — Home Standby Generator Clearances

Exhaust

Port Lifting the Generator

Install the unit where the location of any services such as phone, electrical, fuel, air conditioning, irrigation, including covered, concealed and underground services will not be affected or obstructed.

Install the unit where air inlet and outlet openings will not become obstructed by leaves, grass, snow, etc. If prevailing winds will cause blowing or drifting, you may need to construct a windbreak to protect the unit.

Install the generator as close as possible to the Transfer Switch to reduce the length of wiring and conduit.

Install the generator as close as possible to the fuel supply to reduce length of pipes.

IMPORTANT: Laws or local codes may regulate the distance to the fuel supply.

The Home Standby Generator is shipped already attached to its mounting pad. Unless mandated by local code, a concrete slab is not required.

If mandated by local code, construct a concrete slab at least 3 inches thick and 6 inches longer and wider than the unit. Attach unit to slab with 1/4” diameter (minimum) masonry anchor bolts long enough to retain the unit.

Fuel and Electrical Inlet Dimensions

Figure 2, below, depicts the location of the fuel piping connector. Also shown is the recommended location for punching holes for attaching the power conduit.

Lifting the Generator

The generator weighs more than 375 pounds. Proper tools, equipment and qualified personnel should be used in all phases of handling and moving the generator.

Hazardous Voltage WARNING

Hazardous Voltage

Contact with power lines can cause electric shock or burn.

Lifting Hazard / Heavy Object

Can cause muscle strain or back injury.

If lifting or hoisting equipment is used, DO NOT contact any power lines.

DO NOT lift or move generator without assistance.

Use lifting pipes as described in the section “Lifting the Generator” in installation manual.

The unit may shift on the lifting pipes during movement, which can cause injury.

DO NOT lift unit by roof as damage to generator will occur.

Figure 2 — Generator Fuel and Conduit Attachment Locations, Oil Service Side of Unit

Fuel Piping

Connector

4.5”

Recommended

 

Conduit Attachment

3/4” NPT

Area

13.5”

5

Page 5
Image 5
Briggs & Stratton 01815-0, 01938-0 manual Fuel and Electrical Inlet Dimensions, Lifting the Generator, Hazardous Voltage