Maintenance

The transfer switch is designed to be maintenance free under normal usage. However, inspection and maintenance checks should be made on a regular basis. Maintenance will consist mainly of keeping the transfer switch clean.

Visual inspections should be done at least once a month. Access to transfer switch must not be obstructed. Keep

3 feet (1 m) clearance around transfer switch. Check for an accumulation of dirt, moisture and/or corrosion on and

around the enclosure, loose parts/hardware, cracks and/or discoloration to insulation, and damaged or discolored components.

Exercise the transfer switch at least once every three months as described in section Testing the Automatic Transfer Switch unless a power outage occurs and home generator system has gone through an automatic sequence. Allow generator to run for at least 30 minutes.

Contact a licensed electrical professional to inspect and clean the inside of your transfer switch at least once a year.

Specifications

UL® 1008 Listed Transfer Switch

 

 

Model 071018

 

Model 071020

 

Maximum Load Current .

. . . . . . . . . . . . . . . . . . . .100 Amps

Maximum Load Current .

. . . . . . . . . . . . . . . . . . . .100 Amps

Rated AC Voltage

. . . . . . . . . . . . . . . . . . . . .250 Volts

Rated AC Voltage

. . . . . . . . . . . . . . . . . . . . .250 Volts

Poles

. . . . . . . . . . . . . . . . . . . . . . . . . . .2

Poles

. . . . . . . . . . . . . . . . . . . . . . . . . . .2

Frequency

. . . . . . . . . . . . . . . . . . . . .50/60 Hz

Frequency

. . . . . . . . . . . . . . . . . . . . .50/60 Hz

Fault Current Rating . . . .

22,000 RMS Symmetrical Amperes

Fault Current Rating . . . .

22,000 RMS Symmetrical Amperes

Supervisory Contacts Rating:

Supervisory Contacts Rating:

A-A Terminals

. . . . . . . . . . . . . . . . . . . .24 Volt AC

A-A Terminals

. . . . . . . . . . . . . . . . . . . .24 Volt AC

B-B Terminals

. . . .1 Amp, 125 Volt AC, Pilot Duty

B-B Terminals

. . . .1 Amp, 125 Volt AC, Pilot Duty

Weight

. . . . . . . . . . . . . . . . . . . . . . .21 lbs.

Weight

. . . . . . . . . . . . . . . . . . . . . . .32 lbs.

Model 071019

 

Model 071021

 

Maximum Load Current .

. . . . . . . . . . . . . . . . . . . .200 Amps

Maximum Load Current .

. . . . . . . . . . . . . . . . . . . .200 Amps

Rated AC Voltage

. . . . . . . . . . . . . . . . . . . . .250 Volts

Rated AC Voltage

. . . . . . . . . . . . . . . . . . . . .250 Volts

Poles

. . . . . . . . . . . . . . . . . . . . . . . . . . .2

Poles

. . . . . . . . . . . . . . . . . . . . . . . . . . .2

Frequency

. . . . . . . . . . . . . . . . . . . . .50/60 Hz

Frequency

. . . . . . . . . . . . . . . . . . . . .50/60 Hz

Fault Current Rating . . . .

25,000 RMS Symmetrical Amperes

Fault Current Rating . . . .

25,000 RMS Symmetrical Amperes

Supervisory Contacts Rating:

Supervisory Contacts Rating:

A-A Terminals

. . . . . . . . . . . . . . . . . . . .24 Volt AC

A-A Terminals

. . . . . . . . . . . . . . . . . . . .24 Volt AC

B-B Terminals

. . . .1 Amp, 125 Volt AC, Pilot Duty

B-B Terminals

. . . .1 Amp, 125 Volt AC, Pilot Duty

Weight

. . . . . . . . . . . . . . . . . . . . . . .34 lbs.

Weight

. . . . . . . . . . . . . . . . . . . . . . .44 lbs.

9

Page 11
Image 11
Briggs & Stratton 71018 Maintenance, Specifications, UL 1008 Listed Transfer Switch Model, Supervisory Contacts Rating