11NO PREVIOUS CODE – Stored codes are erased after 72 hours. On RED LED boards stored status codes can also be

erased whenever power (115V or 24V) is interrupted. Run system through a heating or cooling cycle to check system.

12BLOWER ON AFTER POWER UP – (115V OR 24V) – Normal operation.

Blower runs for 90 seconds, if unit is powered up during a call for heat (R-W closed) or when (R-W opens) during the blower on-delay period.

13LIMIT CIRCUIT LOCKOUT – Lockout occurs if the limit, draft safeguard, flame rollout, or blocked vent switch*(if used) is open longer than 3 minutes. Control will auto-reset after 3 hours. See code 33.

14IGNITION LOCKOUT – System failed to ignite gas and prove flame in 4 attempts.

Control will auto-reset after 3 hours. See status code 34.

21GAS HEATING LOCKOUT – Turn off power and wait 5 minutes to retry. Check for:

-Stuck closed gas valve relay on control.

-Miswire or short to gas valve wire.

22ABNORMAL FLAME-PROVING SIGNAL Flame is proved while gas valve is de-

energized. Inducer will run until fault is cleared. Check for:

- Stuck open or leaky gas valve.

31PRESSURE SWITCH DID NOT CLOSE OR REOPENED – If open longer than 5 minutes, inducer shuts off for 15 minutes before retry. If opens during blower on- delay period, blower will come on for the selected blower off-delay. Check for:

-Proper vent sizing.

-Low inducer voltage (115V).

-Low inlet gas pressure (if LGPS used).

-Inadequate combustion air supply.

-Disconnected or obstructed pressure tubing.

-Defective inducer motor.

-Defective pressure switch.

-Excessive wind.

-Restricted vent.

33LIMIT CIRCUIT FAULT – Indicates the limit, draft safeguard, flame rollout, or

blocked vent switch* (if used) is open.

 

Blower will run for 4 minutes or until open

 

switch remakes whichever is longer. If

 

open longer than 3 minutes, code

 

changes to lockout #13. If open less

 

than 3 min. status code #33 continues

 

to flash until blower shuts off. Flame

 

rollout switch and BVSS requires manual

 

reset. Check for:

 

- Dirty filter or restricted duct system.

 

-

Loose blower wheel.

 

- Defective switch or connections.

 

- Defective blower motor or capacitor.

 

- Inadequate combustion air supply

 

 

(flame rollout switch open).

 

-

Restricted vent.

 

-

Proper vent sizing.

 

-

Excessive wind.

 

34 IGNITION PROVING FAILURE – If flame

 

is not sensed during the trial for ignition

 

period, the control will repeat the ignition

 

NO

sequence 3 more times before lockout

 

#14 occurs. If flame signal is lost during

 

Unplug igniter harness from control and initiate another component test sequence. Check for 115V between pin 1 and NEUTRAL-L2 on the control. Was 115V present for the 15 second period?

Reconnect the R thermostat lead and set thermostat to call for heat. Connect voltmeter across gas valve connections. Does gas valve receive 24V?

YES

Does gas valve open and allow gas to flow?

YES

Do the main burners ignite?

YES

Do the main burners stay on?

NO

Repeat call for heat and check flame sensor current during trial for ignition period. Is the DC microamps below 0.5?

YES

45CONTROL CIRCUITRY LOCKOUT Auto-reset after 1 hour lockout due to:

-Flame circuit failure.

- Gas valve relay stuck open.

-Software check error.

Reset power to clear lockout. Replace control if code repeats.

NO

Replace furnace control.

YES

 

Check for continuity in the harness and igniter.

 

 

 

Replace defective component.

NO

 

Check connections. If OK, replace control.

 

 

 

 

 

 

 

 

Check that all gas valves are turned on.

 

 

 

Replace valve.

 

 

 

Check for:

NO

 

 

- Inadequate flame carryover or rough

 

 

 

 

 

 

ignition.

NO

 

- Low inlet gas pressure.

 

- Proper firing rate.

 

 

 

 

 

 

 

 

 

- Blocked or incorrect carry- over gap.

 

 

 

(.045” nominal)

YES

 

Allow blower to come on and repeat test to

 

 

 

 

 

 

check for intermittent operation.

NO

 

Check connections and retry. If current is

 

near typical value (4.0-6.0 nominal) and

 

 

 

 

 

 

burners will not stay on, replace control.

23PRESSURE SWITCH DID NOT OPEN Check for:

-Obstructed pressure tube.

-Pressure switch stuck closed.

24SECONDARY VOLTAGE FUSE IS OPEN Check for:

-Short circuit in secondary voltage (24V) wiring including thermostat leads. Disconnect thermostat leads to isolate short circuit.

the blower on-delay period, blower will

YES

come on for the selected blower off-delay.

 

 

Check the following items first before proceeding to the next step.

-Gas valve turned off.

-Manual shut-off valve.

-Green/Yellow wire MUST be connected to furnace sheet metal.

-Flame sensor must not be grounded. To determine whether the problem is in the gas valve, igniter, or flame sensor the system can be operated in the component test mode to check the igniter. First remove the R thermostat connection from the control and initiate the component test sequence. Does the igniter glow orange/white by the end of the 15 second warm-up period?

*Blocked vent switch used in Chimney Adapter Kit

Clean flame sensor with fine steel wool and recheck current. Nominal current is 4.0 to 6.0 microamps.

Is current near typical value?

YES

Will main burners ignite and stay on?

YES

Fixed.

NO

Replace electrode.

NO

Replace furnace control.

 

A02106b