Make field power connections directly to line connection pressure lugs only.

!WARNING

FIRE HAZARD

Failure to follow this warning could result in intermittent operation or performance satisfaction.

Do not connect aluminum wire between disconnect switch and furnace. Use only copper wire.

(See Fig. 21.)

548J*14D

C10014

Fig. 19 - Mounting Position for Field Disconnects

(over 100A)

C10013

Fig. 20 - Mounting Position for Field Disconnects

(up to 100A)

All units except 208/230-v units are factory wired for the voltage shown on the nameplate. If the 208/230-v unit is to be connected to a 208-v power supply, the control transformer must be rewired by moving the black wire with the 1/4-in. female spade connector from the 230-v connection and moving it to the 200-v1/4-in. male terminal on the primary side of the transformer. Refer to unit label diagram for additional information.

Field power wires are connected to the unit at line-side pressure lugs at the main terminal block (TB1) or at factory-installed option non-fused disconnect switch. Max wire size is #2 AWG (copper only). (See Fig. 22)

NOTE: TEST LEADS - Unit may be equipped with short leads (pigtails) on the field line connection points off the optional disconnect switch. These leads are for factory run-test purposes only; remove and discard before connecting field power wires to unit connection points.

ELECTRIC

DISCONNECT

SWITCH

COPPER

WIRE ONLY

ALUMINUM

WIRE

A93033

Fig. 21 - Disconnect Switch and Unit

All Units -

All field wiring must comply with the NEC and local requirements.

Size wire based on MCA (Minimum Circuit Amps) on the unit informative plate. See Fig. 22 and the unit label diagram for power wiring connections to the unit power terminal blocks and equipment ground. Maximum wire size is #2/0 AWG per pole.

Provide a ground-fault and short-circuit over-current protection device (fuse or breaker) per NEC Article 440 (or local codes). Refer to unit informative data plate for MOCP (Maximum Over-current Protection) device size.

Voltage to compressor terminals during operation must be within voltage range indicated on unit nameplate. See Table 4. On 3-phase units, voltages between phases must be balanced within 2% and the current within 10%. Use the formula shown in the legend for Table 4 (see Note 2 on page 32) to determine the percent of voltage imbalance.

!CAUTION

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment damage.

Operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical components. Such operation would invalidate any applicable Bryant warranty.

12

Page 12
Image 12
Bryant 548J*14D installation instructions Mounting Position for Field Disconnects Over 100A

548J*14D specifications

The Bryant 548J*14D is a highly efficient and versatile air conditioning unit designed to meet the varying demands of residential and light commercial applications. This model stands out due to its advanced engineering, energy-saving features, and reliable performance, making it an ideal choice for homeowners looking to enhance comfort without compromising on energy efficiency.

One of the main features of the Bryant 548J*14D is its excellent SEER (Seasonal Energy Efficiency Ratio) rating, which signifies its ability to provide cooling while consuming less energy. Optimized for efficiency, this unit employs a high-efficiency compressor that adjusts its output based on cooling demands, allowing it to use only the energy necessary to maintain a comfortable environment.

The unit’s all-aluminum evaporator coil ensures durability and resistance to corrosion, contributing to its longer lifespan and consistent performance. Additionally, the Bryant 548J*14D incorporates advanced refrigeration technologies for maximum heat transfer efficiency. This technology not only enhances cooling performance but also improves overall system reliability.

A key characteristic of the Bryant 548J*14D is its Whisper Series technology designed for quiet operation. The low-noise design minimizes sound levels, allowing for unobtrusive cooling in residential spaces while still ensuring effective airflow and cooling capacity. This makes it particularly favorable for installation in bedrooms and other noise-sensitive areas.

Another noteworthy aspect of the Bryant 548J*14D is its compatibility with the MyBryant smartphone app, which enables homeowners to monitor and control their HVAC systems remotely. This connectivity offers convenience and helps to optimize energy usage, as users can adjust settings based on their schedules and preferences.

Furthermore, the Bryant 548J*14D is designed with a robustness that allows it to withstand diverse weather conditions, ensuring reliable performance even in extreme climates. The unit’s compact design eases installation in various settings, whether it's on rooftops, near walls, or on concrete pads.

In summary, the Bryant 548J*14D is a cutting-edge air conditioning unit that combines energy efficiency, quiet operation, and advanced technologies. With its robust construction, smart features, and reliable performance, it stands as a valuable solution for anyone looking to enhance comfort and save on energy costs in their homes or light commercial environments.