Bryant 548J*14D Unit Powered Convenience Outlet Wiring, Weatherproof Cover Installation, Voltage

Models: 548J*14D

1 36
Download 36 pages 7.83 Kb
Page 14
Image 14
VOLTAGE

548J*14D

the transformer; however, the conduit must be routed so that all wiring is either in the conduit or behind the access panel.

If the convenience outlet transformer is connected to the line side of the factory disconnect option, route the wires through the web bushing located on the bottom of the disconnect box. For the load side wiring to the factory option disconnect, route the wires through the hole on the right side of the disconnect. Be sure to create a drip loop at least 6” long.

Duty Cycle: the unit-powered convenience outlet has a duty cycle limitation. The transformer is intended to provide power on an intermittent basis for service tools, lamps, etc; it is not intended to provide 15-amps loading for continuous duty loads (such as electric heaters for overnight use). Observe a 50% limit on circuit loading above 8-amps (i.e., limit loads exceeding 8-amps to 30 minutes of operation every hour).

Test the GFCI receptacle by pressing the TEST button on the face of the receptacle to trip and open the receptacle. Check for proper grounding wires and power line phasing if the GFCI receptacle does not trip as required. Press the RESET button to clear the tripped condition.

C08283

UNIT

CONNECT

PRIMARY

TRANSFORMER

VOLTAGE

AS

CONNECTIONS

TERMINALS

 

 

 

 

208,

240

L1: RED +YEL

H1 + H3

230

L2: BLU + GRA

H2 + H4

 

 

 

 

 

 

 

L1: RED

H1

460

480

Splice BLU + YEL

H2 + H3

 

 

L2: GRA

H4

 

 

 

 

575

600

L1: RED

H1

L2: GRA

H2

 

 

 

 

 

 

Fig. 24 - Unit Powered Convenience Outlet Wiring

Fuse on power type: The factory fuse is a Bussman “Fusetron” T-15, non-renewable screw-in (Edison base) type plug fuse.

!WARNING

ELECTRICAL OPERATION HAZARD

Failure to follow this warning could result in personal injury or death.

Using unit-mounted convenience outlets: Units with unit-mounded convenience outlet circuits will often require that two disconnects be opened to de-energize all power to the unit. Treat all units as electrically energized until the convenience outlet power is also checked and de-energization is confirmed. Observe National Electrical Code Article 210, Branch Circuits, for use of convenience outlets.

Installing Weatherproof Cover: A weatherproof while-in-use cover for the factory-installed convenience outlets is now required by UL standards. This cover cannot be factory-mounted due its depth; it must be installed at unit installation. For shipment, the convenience outlet is covered with a blank cover plate.

The weatherproof cover kit is shipped in the unit’s control box. The kit includes the hinged cover, a backing plate and gasket.

DISCONNECT ALL POWER TO UNIT AND CONVENIENCE OUTLET.

Remove the blank cover plate at the convenience outlet; discard the blank cover.

Loosen the two screws at the GFCI duplex outlet, until approximately 1/2-in (13 mm) under screw heads are exposed. Press the gasket over the screw heads. Slip the backing plate over the screw heads at the keyhole slots and align with the gasket; tighten the two screws until snug (do not over-tighten).

Mount the weatherproof cover to the backing plate as shown in Fig. 25. Remove two slot fillers in the bottom of the cover to permit service tool cords to exit the cover. Check for full closing and latching.

COVER – WHILE-IN-USE

RECEPTACLE

WEATHERPROOF
NOT INCLUDED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BASE PLATE FOR

GFCI RECEPTACLE

C09022

Fig. 25 - Weatherproof Cover Installation

14

Page 14
Image 14
Bryant 548J*14D Unit Powered Convenience Outlet Wiring, Weatherproof Cover Installation, Electrical Operation Hazard