548J*14D
the transformer; however, the conduit must be routed so that all wiring is either in the conduit or behind the access panel.
If the convenience outlet transformer is connected to the line side of the factory disconnect option, route the wires through the web bushing located on the bottom of the disconnect box. For the load side wiring to the factory option disconnect, route the wires through the hole on the right side of the disconnect. Be sure to create a drip loop at least 6” long.
Duty Cycle: the
Test the GFCI receptacle by pressing the TEST button on the face of the receptacle to trip and open the receptacle. Check for proper grounding wires and power line phasing if the GFCI receptacle does not trip as required. Press the RESET button to clear the tripped condition.
C08283 |
UNIT | CONNECT | PRIMARY | TRANSFORMER | |
VOLTAGE | AS | CONNECTIONS | TERMINALS | |
|
|
|
| |
208, | 240 | L1: RED +YEL | H1 + H3 | |
230 | L2: BLU + GRA | H2 + H4 | ||
| ||||
|
|
|
| |
|
| L1: RED | H1 | |
460 | 480 | Splice BLU + YEL | H2 + H3 | |
|
| L2: GRA | H4 | |
|
|
|
| |
575 | 600 | L1: RED | H1 | |
L2: GRA | H2 | |||
|
| |||
|
|
|
|
Fig. 24 - Unit Powered Convenience Outlet Wiring
Fuse on power type: The factory fuse is a Bussman “Fusetron”
!WARNING
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal injury or death.
Using
Installing Weatherproof Cover: A weatherproof
The weatherproof cover kit is shipped in the unit’s control box. The kit includes the hinged cover, a backing plate and gasket.
DISCONNECT ALL POWER TO UNIT AND CONVENIENCE OUTLET.
Remove the blank cover plate at the convenience outlet; discard the blank cover.
Loosen the two screws at the GFCI duplex outlet, until approximately
Mount the weatherproof cover to the backing plate as shown in Fig. 25. Remove two slot fillers in the bottom of the cover to permit service tool cords to exit the cover. Check for full closing and latching.
COVER – | RECEPTACLE | |||||
WEATHERPROOF | ||||||
NOT INCLUDED | ||||||
|
|
|
|
|
| |
|
|
|
|
|
| |
|
|
|
|
|
| |
|
|
|
|
|
|
BASE PLATE FOR
GFCI RECEPTACLE
C09022
Fig. 25 - Weatherproof Cover Installation
14