Bryant 548J*14D Completing Installation of Return Air Smoke Sensor, Additional Application Data

Models: 548J*14D

1 36
Download 36 pages 7.83 Kb
Page 29
Image 29
Completing Installation of Return Air Smoke Sensor:

Completing Installation of Return Air Smoke Sensor:

1.Unscrew the two screws holding the Return Air Sensor detector plate. See Fig. 53. Save the screws.

2.Remove the Return Air Sensor and its detector plate.

3.Rotate the detector plate so the sensor is facing out- wards and the sampling tube connection is on the bot- tom. See Fig. 54.

4.Screw the sensor and detector plate into its operating position using screws from Step 1. Make sure the sampling tube connection is on the bottom and the ex- haust tube is on the top. See Fig. 54.

5.Connect the flexible tube on the sampling inlet to the sampling tube on the basepan.

Controller

Fig. 53 - Return Air Detector Shipping Position Screws

Flexible

Exhaust

Tubes

Sampling Tube

C10331

Fig. 53 - Return Air Detector Shipping Position

Sampling Tube

C10332

Fig. 54 - Return Air Sensor Operating Position

Additional Application Data —

Refer to Catalog No. HKRNKA-1XA for discussions on additional control features of these smoke detectors including multiple unit coordination.

548J*14D

29

Page 29
Image 29
Bryant 548J*14D Completing Installation of Return Air Smoke Sensor, Return Air Detector Shipping Position