Bryant manual WEIGHTS & DIMENSIONS cont, Dimensions 548J, Service Clearance

Models: 548J

1 76
Download 76 pages 14.11 Kb
Page 19
Image 19
WEIGHTS & DIMENSIONS (cont.)

WEIGHTS & DIMENSIONS (cont.)

548J

C

B

C09019

Fig. 2 - Dimensions 548J 04-07

D

A

C08337

 

 

Fig. 3 - Service Clearance

 

 

 

LOC

DIMENSION

CONDITION

 

48” (1219 mm)

Unit disconnect is mounted on panel

A

18” (457 mm)

No disconnect, convenience outlet option

18” (457 mm)

Recommended service clearance

 

 

12” (305 mm)

Minimum clearance

 

 

 

 

42” (1067 mm)

Surface behind servicer is grounded (e.g., metal, masonry wall)

B

36” (914 mm)

Surface behind servicer is electrically non---conductive (e.g., wood, fiberglass)

 

Special

Check for sources of flue products within 10---ft of unit fresh air intake hood

 

 

 

C

36” (914 mm)

Side condensate drain is used

18” (457 mm)

Minimum clearance

 

 

 

 

D

42” (1067 mm)

Surface behind servicer is grounded (e.g., metal, masonry wall, another unit)

36” (914 mm)

Surface behind servicer is electrically non---conductive (e.g., wood, fiberglass)

 

 

 

 

19

Page 19
Image 19