548J
Table 2 – ARI COOLING RATING TABLES
|
|
| COOLING MODE |
|
|
|
| NOMINAL | NET COOLING | TOTAL |
|
|
|
548J* | CAPACITY | CAPACITY | POWER | SEER | EER | IPLV |
| (TONS) | (BTUH) | (kW) |
|
|
|
|
|
|
|
|
|
|
04A | 3 | 37,000 | 3.3 | 13.40** | 11.00 | N/A |
05A | 4 | 47,000 | 4.1 | 13.10** | 11.20 | N/A |
|
|
|
|
|
|
|
06A | 5 | 61,500 | 5.5 | 13.20** | 11.15 | N/A |
07A | 6 | 70,000 | 6.3 | N/A | 11.10 | N/A |
|
|
|
|
|
|
|
08D | 7.5 | 88,000 | 7.8 | N/A | 11.20 | 12.40 |
09D | 8.5 | 99,000 | 8.8 | N/A | 11.20 | 12.40 |
NOTE:
All AHRI ratings are based on 230, 460 and 575 volt.
**Electric Drive (direct drive) X13 5 speed/torque motor. SEER rating is 13.0 for belt drive.
NA Not applicable
|
| HEATING MODE |
|
|
|
| |
548J* | HSPF | HEATING, LOW |
| HEATING, HIGH |
| ||
CAPACITY |
| COP | CAPACITY |
| COP | ||
|
| (BTUH) |
| (BTUH) |
| ||
|
|
|
|
|
| ||
04A | 7.70 | 18,200 |
| N/A | 35,600 |
| N/A |
05A | 7.70 | 23,600 |
| N/A | 45,500 |
| N/A |
06A | 7.70 | 31,200 |
| N/A | 58,000 |
| N/A |
07A | N/A | 34,800 |
| 2.25 | 67,000 |
| 3.30 |
08D | N/A | 48,000 |
| 2.25 | 86,000 |
| 3.30 |
09D | N/A | 54,500 |
| 2.25 | 96,000 |
| 3.30 |
LEGEND |
|
|
ARI | ||
|
| Institute |
ASHRAE | ||
|
| and Air Conditioning, Inc. |
COP | Coefficient of Performance | |
EER | Energy Efficiency Ratio | |
HSPF | Heating Seasonal Performance Factor | |
IPLV | ||
SEER |
NOTES:
1.Rated and certified under ARI Standard
2.Ratings are based on:
Cooling Standard: 80_F (27_C) db, 67_F (19_C) wb indoor air temp and 95_F db outdoor air temp.
IPLV Standard: 80_F (27_C) db, 67_F (19_C) wb indoor air temp and 80_F (27_C) db outdoor air temp.
3.All 548J units comply with ASHRAE 90.1 2001, 2004 Energy Standard for minimum SEER and EER requirements.
4.Where appropriate, 548J units comply with US Energy Policy Act (2005). Refer to state and local codes or visit the following website:
This product has been designed and manufactured to meet Energy Star® criteria for energy efficiency. However, proper refrigerant charge and proper air flow are critical to achieve rated capacity and efficiency. Installation of this product should follow all manufacturer’s refrigerant charging and air flow
instructions. Failure to confirm proper charge and air flow may reduce energy efficiency and shorten equipment life.
8