Bryant manual SELECTION PROCEDURE WITH 548J*07 EXAMPLE

Models: 548J

1 76
Download 76 pages 14.11 Kb
Page 25
Image 25
SELECTION PROCEDURE (WITH 548J*07 EXAMPLE)

SELECTION PROCEDURE (WITH 548J*07 EXAMPLE)

(Selection software by Bryant saves time by performing many of the steps below.)

I.Determine cooling and heating loads.

Given:

 

Mixed Air Drybulb

80_F (27_C)

Mixed Air Wetbulb

67_F (19_C)

Ambient Drybulb

95_F (35_C)

TCLoad

65.0 MBH

SHCLoad

46.0 MBH

HCLoad

45.0 MBH

Outdoor-Air Winter Design Temp

0_F (-18_C)

Indoor-Air Winter Design Temp

70_F (21_C)

Vertical Supply Air

2100 CFM

External Static Pressure

0.66 in.wg

Electrical Characteristics

230-3-60

II.Make an initial guess at cooling tons.

Refrig. tons = TCLoad / 12 MBH per ton Refrig. tons = 65.0 / 12 = 5.42 tons

In this case, start by looking at the 548J*07.

III. Look up the rooftop’s TC and SHC.

Table 11 shows that, at the application’s supply air CFM, mixed air and ambient temperatures, the

548J*07 supplies: TCLoad = 69.0 MBH SHCLoad = 50.7 MBH.

The required heating capacity is 45,000 Btuh. There- fore, 20,700 Btuh (45,000 – 24,300) additional elec- tric heat is required.

Determine additional electric heat capacity in kW.

20,700 Btuh

= 6.1 kW of heat required.

 

3413 Btuh/kW

 

Enter the Electric Heating Capacities table for 548J*07 at 208/230, 3-phase. The 6.5-kW heater at 230V most closely satisfies the heating required.

6.5 kW x 3413 = 22,185 Btuh

Total unit heating capacity is 46,485 Btuh (22,185 + 24,300).

VI. Calculate RTU Latent Heat Capacity

LC = TC - SHC

LC = 69.0 MBH - 50.7 MBH = 18.3 MBH

VII. Compare RTU capacities to loads.

Compare the rooftop’s SHC and LC to the building’s Sensible and Latent Heat Loads.

See Notes 1 and 2.

VIII. Select factory options (FIOP)

Local code requires an economizer for any unit with TC larger than 65.0 MBH.

548J

IV. Calculate the building Latent Heat Load.

LCLoad = TCLoad - SHCLoad

LCLoad = 65.0 MBH - 46.0 MBH = 19.0 MBH

V.Select electric heat.

Enter the Instantaneous and Integrated Heating Rat- ings, Table 17 at 2100 cfm. At 70_F (21_C) return indoor air and 0°F (-18_C) air entering outdoor coil, the integrated heating capacity after interpolation, is 24,300 Btuh. (Select integrated heating capacity value since deductions for outdoor-coil frost and de- frosting have already been made. No correction is re- quired.)

IX. Calculate the total static pressure.

 

External static pressure

0.66 in. wg

Sum of FIOP/Accessory static

+0.14 in. wg

Total Static Pressure

0.80 in. wg

X.Look up the Indoor Fan RPM & BHP.

Table 34 shows, at 2100 CFM & ESP= 0.8, RPM = 1268 & BHP = 1.52

XI. Determine electrical requirements

Table 25 shows the MCA and MOCP of a 548J*07 (without convenience outlet) with 6.5 kW electric heater as:

MCA = 52.3 amps & MOCP = 60 amps

Min. Disconnect Size: FLA = 50 & LRA = 199.

Legend

 

 

NOTES:

BHP

Break horsepower

1. Selecting a unit with a SHC slightly lower than the SHCLoad is

FLA

Full load amps

often better than oversizing. Slightly lower SHC’s will help con-

HC

Heating Capacities

trol indoor humidity, and prevent temperature swings.

LC

Latent capacity

2. If the rooftop’s capacity meets the Sensible Heat Load, but not

the Latent Heat Load.

LRA

Lock rotor amp

 

MBH

(1,000) BTUH

 

MCA

Min. circuit ampacity

 

MOCP

Max. over---current protection

 

RPM

Revolutions per minute

 

RTU

Rooftop unit

 

SHC

Sensible heat capacity

 

TC —

Total capacity

 

25

Page 25
Image 25
Bryant manual SELECTION PROCEDURE WITH 548J*07 EXAMPLE