Operation
80
3.3.7 Emergency Modules Off

The Local Emergency Modules Off (LEMO) mode is used to remove power from all UPS system com-

ponents and the critical load will continue to be supplied through the bypass line.

The Emergency Module Off control is a guarded pad on the SCC Control Panel (see Figure10).

Lift the cover and press the pad. The load will be transferred to bypass and the battery (MBD), input

and output circuit breakers will be opened (tripped). This will remove power from all UPS system

components except the controls, system bypass circuit breaker and the static switch.

Refer to 3.4.5 - Shutdown Procedures.

Figure 59 Emergency modules off

BIB
SKRU
MIB
MBB
I
R
#2UPS
CB1
CB2
System
Controls
RIB RIB RIB BFB
Output
SBB
SBS
RIB RIB RIB BFB
#1UPS#3UPS
I
R
#1UPS
CB1
I
R
#3UPS
CB1
CB2 CB2
SCCT
SCCT
(canaccommodate up to 6 UPS modules)
ToCritical Load
Battery
MBD
Battery
MBD
Battery
MBD